A generic device designed to close, or open, or both, one or more electric circuits. All switches are two terminal devices including grounding switches. The ACDCTerminal.connected at the two sides of the switch shall not be considered for assessing switch connectivity, i.e. only Switch.open, .normalOpen and .locked are relevant.
Same definition as SwitchA ProtectedSwitch is a switching device that can be operated by ProtectionEquipment.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Array of Terminal objects
No Additional ItemsAn AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.
No Additional PropertiesThe connected status is related to a bus-branch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not.
In a bus-branch model, the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment, where the reactive line charging can be significant, this is a relevant case.
Represents the normal network phasing condition. If the attribute is missing, three phases (ABC) shall be assumed, except for terminals of grounding classes (specializations of EarthFaultCompensator, GroundDisconnector, and Ground) which will be assumed to be N. Therefore, phase code ABCN is explicitly declared when needed, e.g. for star point grounding equipment.
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.
The orientation of the terminal connections for a multiple terminal conducting equipment. The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the "starting point" for a two terminal branch.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Array of SvSwitch objects
No Additional ItemsState variable for switch.
No Additional PropertiesThe terminal phase at which the connection is applied. If missing, the injection is assumed to be balanced among non-neutral phases.
The attribute tells if the computed state of the switch is considered open.
If true, the switch is not ganged (i.e., a switch phase may be operated separately from other phases).
Gas or air pressure at or below which a low pressure alarm is generated.
nan
nan
nan
Rated impulse withstand voltage, also known as BIL (Basic Impulse Level).
nan
If true, it is a single phase switch.
Switch rated interrupting time in seconds.
Time, in seconds
Volume of oil in each tank of bulk oil breaker.
nan
Weight of gas in each tank of SF6 dead tank breaker.
nan
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The maximum fault current a breaking device can break safely under prescribed conditions of use.
nan
Gas or air pressure below which the breaker will not open.
Same definition as SwitchInfo.lowPressureAlarmFrequency for which switch is rated.
nan
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Pointer to BaseVoltage object
Array of SwitchPhase objects
No Additional ItemsSingle phase of a multi-phase switch when its attributes might be different per phase.
No Additional PropertiesUsed in cases when no Measurement for the status value is present. If the SwitchPhase has a status measurement the Discrete.normalValue is expected to match with this value.
Phase of this SwitchPhase on the side with terminal sequence number equal to 1. Should be a phase contained in that terminal’s phases attribute.
Same definition as SvSwitch.phasePhase of this SwitchPhase on the side with terminal sequence number equal to 2. Should be a phase contained in that terminal’s Terminal.phases attribute.
Same definition as SvSwitch.phaseUsed in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered closed when used as input to topology processing.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Array of SvStatus objects
No Additional ItemsState variable for status.
No Additional PropertiesThe in service status as a result of topology processing. It indicates if the equipment is considered as energized by the power flow. It reflects if the equipment is connected within a solvable island. It does not necessarily reflect whether or not the island was solved by the power flow.
The individual phase status. If the attribute is unspecified, then three phase model is assumed.
Same definition as SvSwitch.phaseThe transition time from open to close.
Same definition as SwitchInfo.ratedInterruptingTimeThe maximum fault current a breaking device can break safely under prescribed conditions of use.
Same definition as SwitchInfo.breakingCapacityThe aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A mechanical switching device capable of making, carrying, and breaking currents under normal circuit conditions and also making, carrying for a specified time, and breaking currents under specified abnormal circuit conditions e.g. those of short circuit.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The transition time from open to close.
Same definition as SwitchInfo.ratedInterruptingTimeThe maximum fault current a breaking device can break safely under prescribed conditions of use.
Same definition as SwitchInfo.breakingCapacityThe aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A mechanical switching device capable of making, carrying, and breaking currents under normal operating conditions.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The maximum fault current a breaking device can break safely under prescribed conditions of use.
Same definition as SwitchInfo.breakingCapacityThe aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Pole-mounted fault interrupter with built-in phase and ground relays, current transformer (CT), and supplemental controls.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The maximum fault current a breaking device can break safely under prescribed conditions of use.
Same definition as SwitchInfo.breakingCapacityThe aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A cut separates a line segment into two parts. The cut appears as a switch inserted between these two parts and connects them together. As the cut is normally open there is no galvanic connection between the two line segment parts. But it is possible to close the cut to get galvanic connection.
The cut terminals are oriented towards the line segment terminals with the same sequence number. Hence the cut terminal with sequence number equal to 1 is oriented to the line segment's terminal with sequence number equal to 1.
The cut terminals also act as connection points for jumpers and other equipment, e.g. a mobile generator. To enable this, connectivity nodes are placed at the cut terminals. Once the connectivity nodes are in place any conducting equipment can be connected at them.
Pointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The length to the place where the cut is located starting from side one of the cut line segment, i.e. the line segment Terminal with sequenceNumber equal to 1.
nan
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Automatic switch that will lock open to isolate a faulted section. It may, or may not, have load breaking capability. Its primary purpose is to provide fault sectionalising at locations where the fault current is either too high, or too low, for proper coordination of fuses.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
An overcurrent protective device with a circuit opening fusible part that is heated and severed by the passage of overcurrent through it. A fuse is considered a switching device because it breaks current.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A manually operated or motor operated mechanical switching device used for isolating a circuit or equipment from ground.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A short section of conductor with negligible impedance which can be manually removed and replaced if the circuit is de-energized. Note that zero-impedance branches can potentially be modelled by other equipment types.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
If true, the switch is locked. The resulting switch state is a combination of locked and Switch.open attributes as follows:
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The attribute tells if the switch is considered open when used as input to topology processing.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The attribute is used in cases when no Measurement for the status value is present. If the Switch has a status measurement the Discrete.normalValue is expected to match with the Switch.normalOpen.
The maximum continuous current carrying capacity in amps governed by the device material and construction.
The attribute shall be a positive value.
Branch is retained in the topological solution. The flow through retained switches will normally be calculated in power flow.
The switch on count since the switch was last reset or initialized.
The date and time when the switch was last switched on.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.