LoadResponseCharacteristic

Type: object

Models the characteristic response of the load demand due to changes in system conditions such as voltage and frequency. It is not related to demand response.
If LoadResponseCharacteristic.exponentModel is True, the exponential voltage or frequency dependent models are specified and used as to calculate active and reactive power components of the load model.
The equations to calculate active and reactive power components of the load model are internal to the power flow calculation, hence they use different quantities depending on the use case of the data exchange.
The equations for exponential voltage dependent load model injected power are:
pInjection= Pnominal* (Voltage/cim:BaseVoltage.nominalVoltage) * cim:LoadResponseCharacteristic.pVoltageExponent
qInjection= Qnominal
(Voltage/cim:BaseVoltage.nominalVoltage) * cim:LoadResponseCharacteristic.qVoltageExponent
Where:
1) * means "multiply" and *
is "raised to power of";
2) Pnominal and Qnominal represent the active power and reactive power at nominal voltage as any load described by the voltage exponential model shall be given at nominal voltage. This means that EnergyConsumer.p and EnergyConsumer.q are at nominal voltage.
3) After power flow is solved:
-pInjection and qInjection correspond to SvPowerflow.p and SvPowerflow.q respectively.
- Voltage corresponds to SvVoltage.v at the TopologicalNode where the load is connected.

No Additional Properties

Type: number

Portion of active power load modelled as constant current.

Type: number

Portion of active power load modelled as constant impedance.

Type: number

Portion of active power load modelled as constant power.

Type: number

Exponent of per unit frequency effecting active power.

Type: number

Exponent of per unit voltage effecting real power.

Type: number

Portion of reactive power load modelled as constant current.

Type: number

Portion of reactive power load modelled as constant impedance.

Type: number

Portion of reactive power load modelled as constant power.

Type: number

Exponent of per unit frequency effecting reactive power.

Type: number

Exponent of per unit voltage effecting reactive power.

Type: string

Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: boolean

Indicates the exponential voltage dependency model is to be used. If false, the coefficient model is to be used.
The exponential voltage dependency model consist of the attributes:
- pVoltageExponent
- qVoltageExponent
- pFrequencyExponent
- qFrequencyExponent.
The coefficient model consist of the attributes:
- pConstantImpedance
- pConstantCurrent
- pConstantPower
- qConstantImpedance
- qConstantCurrent
- qConstantPower.
The sum of pConstantImpedance, pConstantCurrent and pConstantPower shall equal 1.