ExternalNetworkInjectionContainer

Type: object

Hash table of ExternalNetworkInjection objects

No Additional Properties

All properties whose name matches the following regular expression must respect the following conditions

Property name regular expression: ^.+$
Type: object

This class represents the external network and it is used for IEC 60909 calculations.

No Additional Properties

Type: string

Pointer to Location object

Type: string

Pointer to SwitchingAction object

Type: array

Array of Terminal objects

No Additional Items

Each item of this array must be:

Type: object

An AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.

No Additional Properties

Type: boolean

The connected status is related to a bus-branch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not.
In a bus-branch model, the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment, where the reactive line charging can be significant, this is a relevant case.

Type: enum (of string)

Represents the normal network phasing condition. If the attribute is missing, three phases (ABC) shall be assumed, except for terminals of grounding classes (specializations of EarthFaultCompensator, GroundDisconnector, and Ground) which will be assumed to be N. Therefore, phase code ABCN is explicitly declared when needed, e.g. for star point grounding equipment.
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.

Must be one of:

  • "ACN"
  • "s2N"
  • "N"
  • "X"
  • "BN"
  • "s12N"
  • "none"
  • "s1"
  • "AC"
  • "ABC"
  • "AB"
  • "s1N"
  • "BC"
  • "XY"
  • "ABCN"
  • "C"
  • "s12"
  • "AN"
  • "XYN"
  • "ABN"
  • "XN"
  • "s2"
  • "CN"
  • "B"
  • "A"
  • "BCN"

Type: integer

The orientation of the terminal connections for a multiple terminal conducting equipment. The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the "starting point" for a two terminal branch.

Type: string

Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: string

Pointer to BaseVoltage object

Type: array

Array of SvStatus objects

No Additional Items

Each item of this array must be:

Type: object

State variable for status.

No Additional Properties

Type: boolean

The in service status as a result of topology processing. It indicates if the equipment is considered as energized by the power flow. It reflects if the equipment is connected within a solvable island. It does not necessarily reflect whether or not the island was solved by the power flow.

Type: enum (of string)

The individual phase status. If the attribute is unspecified, then three phase model is assumed.

Must be one of:

  • "B"
  • "N"
  • "C"
  • "s2"
  • "A"
  • "s1"

Type: object or number

Power Frequency Bias. This is the change in power injection divided by the change in frequency and negated. A positive value of the power frequency bias provides additional power injection upon a drop in frequency.

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

Type: enum (of string) Default: "WPers"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: boolean

Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik"). Used only if short circuit calculations are done according to superposition method.

Type: object or number

Maximum initial symmetrical short-circuit currents (Ik" max) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909.

Type: object or number

Maximum active power of the injection.

Type: number Default: null

nan

Type: object or number

Maximum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.

Type: number Default: null

nan

Type: number

Maximum ratio of zero sequence resistance of Network Feeder to its zero sequence reactance (R(0)/X(0) max). Used for short circuit data exchange according to IEC 60909.

Type: number

Maximum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) max). Used for short circuit data exchange according to IEC 60909.

Type: number

Maximum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) max). Used for short circuit data exchange according to IEC 60909.

Type: object or number

Minimum initial symmetrical short-circuit currents (Ik" min) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909.

Same definition as ExternalNetworkInjection.maxInitialSymShCCurrent

Type: object or number

Minimum active power of the injection.

Same definition as ExternalNetworkInjection.maxP

Type: object or number

Minimum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.

Same definition as ExternalNetworkInjection.maxQ

Type: number

Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik"). Used for short circuit data exchange according to IEC 6090.

Type: number

Minimum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) min). Used for short circuit data exchange according to IEC 60909.

Type: number

Minimum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) min). Used for short circuit data exchange according to IEC 60909.

Type: integer

Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on.

Type: object or number

Voltage factor in pu, which was used to calculate short-circuit current Ik" and power Sk". Used only if short circuit calculations are done according to superposition method.

Type: string

Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: boolean

Specifies the regulation status of the equipment. True is regulating, false is not regulating.

Type: object or number

Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for steady state solutions.

Same definition as ExternalNetworkInjection.maxP

Type: object or number

Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for steady state solutions.

Same definition as ExternalNetworkInjection.maxQ

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.