Generic user of energy - a point of consumption on the power system model.
EnergyConsumer.pfixed, .qfixed, .pfixedPct and .qfixedPct have meaning only if there is no LoadResponseCharacteristic associated with EnergyConsumer or if LoadResponseCharacteristic.exponentModel is set to False.
Generic user of energy - a point of consumption on the power system model.
EnergyConsumer.pfixed, .qfixed, .pfixedPct and .qfixedPct have meaning only if there is no LoadResponseCharacteristic associated with EnergyConsumer or if LoadResponseCharacteristic.exponentModel is set to False.
ConformLoad represent loads that follow a daily load change pattern where the pattern can be used to scale the load with a system load.
No Additional PropertiesPointer to EnergyConsumerSchedule object
Pointer to Location object
Pointer to SwitchingAction object
Array of Terminal objects
No Additional ItemsAn AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.
No Additional PropertiesThe connected status is related to a bus-branch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not.
In a bus-branch model, the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment, where the reactive line charging can be significant, this is a relevant case.
Represents the normal network phasing condition. If the attribute is missing, three phases (ABC) shall be assumed, except for terminals of grounding classes (specializations of EarthFaultCompensator, GroundDisconnector, and Ground) which will be assumed to be N. Therefore, phase code ABCN is explicitly declared when needed, e.g. for star point grounding equipment.
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.
The orientation of the terminal connections for a multiple terminal conducting equipment. The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the "starting point" for a two terminal branch.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Pointer to SwitchingAction object
Pointer to LoadResponseCharacteristic object
Pointer to BaseVoltage object
Array of EnergyConsumerPhase objects
No Additional ItemsA single phase of an energy consumer.
No Additional PropertiesActive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
nan
nan
nan
Active power of the load that is a fixed quantity. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.pFixed active power as per cent of load group fixed active power. Load sign convention is used, i.e. positive sign means flow out from a node.
Normally 0 to 100 on a defined base.
Phase of this energy consumer component. If the energy consumer is wye connected, the connection is from the indicated phase to the central ground or neutral point. If the energy consumer is delta connected, the phase indicates an energy consumer connected from the indicated phase to the next logical non-neutral phase.
Reactive power of the load that is a fixed quantity. Load sign convention is used, i.e. positive sign means flow out from a node.
nan
Fixed reactive power as per cent of load group fixed reactive power. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.pfixedPctReactive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Array of SvStatus objects
No Additional ItemsState variable for status.
No Additional PropertiesThe in service status as a result of topology processing. It indicates if the equipment is considered as energized by the power flow. It reflects if the equipment is connected within a solvable island. It does not necessarily reflect whether or not the island was solved by the power flow.
The individual phase status. If the attribute is unspecified, then three phase model is assumed.
Same definition as EnergyConsumerPhase.phaseFixed reactive power as a percentage of load group fixed reactive power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.pfixedPctActive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Number of individual customers represented by this demand.
Used for Yn and Zn connections. True if the neutral is solidly grounded.
Active power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.pFixed active power as a percentage of load group fixed active power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.pfixedPctThe type of phase connection, such as wye or delta.
Reactive power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.qfixedReactive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
NonConformLoad represents loads that do not follow a daily load change pattern and whose changes are not correlated with the daily load change pattern.
No Additional PropertiesPointer to EnergyConsumerSchedule object
Pointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to LoadResponseCharacteristic object
Pointer to BaseVoltage object
Array of EnergyConsumerPhase objects
Same definition as EnergyConsumer.EnergyConsumerPhaseFixed reactive power as a percentage of load group fixed reactive power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.pfixedPctActive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Number of individual customers represented by this demand.
Used for Yn and Zn connections. True if the neutral is solidly grounded.
Active power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.pFixed active power as a percentage of load group fixed active power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.pfixedPctThe type of phase connection, such as wye or delta.
Same definition as EnergyConsumer.phaseConnectionReactive power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as EnergyConsumerPhase.qfixedReactive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.