A type of conducting equipment that can regulate a quantity (i.e. voltage or flow) at a specific point in the network.
No Additional PropertiesHash table of PowerElectronicsConnection objects
No Additional PropertiesAll properties whose name matches the following regular expression must respect the following conditions
Property name regular expression:^.+$
A connection to the AC network for energy production or consumption that uses power electronics rather than rotating machines.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Array of Terminal objects
No Additional ItemsAn AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.
No Additional PropertiesThe connected status is related to a bus-branch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not.
In a bus-branch model, the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment, where the reactive line charging can be significant, this is a relevant case.
Represents the normal network phasing condition. If the attribute is missing, three phases (ABC) shall be assumed, except for terminals of grounding classes (specializations of EarthFaultCompensator, GroundDisconnector, and Ground) which will be assumed to be N. Therefore, phase code ABCN is explicitly declared when needed, e.g. for star point grounding equipment.
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.
The orientation of the terminal connections for a multiple terminal conducting equipment. The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the "starting point" for a two terminal branch.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A generating unit or battery or aggregation that connects to the AC network using power electronics rather than rotating machines.
An electrochemical energy storage device.
No Additional Propertiesnan
No Additional Propertiesnan
Pointer to Curve object
Full energy storage capacity of the battery. The attribute shall be a positive value.
nan
nan
nan
Amount of energy currently stored. The attribute shall be a positive value or zero and lower than BatteryUnit.ratedE.
Same definition as BatteryUnit.ratedEThe aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
nan
Normally 0 to 100 on a defined base.
The current state of the battery (charging, full, etc.).
Maximum active power limit. This is the maximum (nameplate) limit for the unit.
nan
Minimum active power limit. This is the minimum (nameplate) limit for the unit.
Same definition as PowerElectronicsUnit.maxPSpecifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A photovoltaic device or an aggregation of such devices.
No Additional PropertiesPointer to Curve object
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Maximum active power limit. This is the maximum (nameplate) limit for the unit.
Same definition as PowerElectronicsUnit.maxPMinimum active power limit. This is the minimum (nameplate) limit for the unit.
Same definition as PowerElectronicsUnit.maxPSpecifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A wind generating unit that connects to the AC network with power electronics rather than rotating machines or an aggregation of such units.
No Additional PropertiesPointer to Curve object
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Maximum active power limit. This is the maximum (nameplate) limit for the unit.
Same definition as PowerElectronicsUnit.maxPMinimum active power limit. This is the minimum (nameplate) limit for the unit.
Same definition as PowerElectronicsUnit.maxPSpecifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Pointer to BaseVoltage object
Array of PowerElectronicsConnectionPhase objects
No Additional ItemsA single phase of a power electronics connection.
No Additional PropertiesPhase of this energy producer component. If the energy producer is wye connected, the connection is from the indicated phase to the central ground or neutral point. If the energy producer is delta connected, the phase indicates an energy producer connected from the indicated phase to the next logical non-neutral phase.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Active power injection. Load sign convention is used, i.e. positive sign means flow into the equipment from the network.
Same definition as PowerElectronicsUnit.maxPReactive power injection. Load sign convention is used, i.e. positive sign means flow into the equipment from the network.
nan
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Array of SvStatus objects
No Additional ItemsState variable for status.
No Additional PropertiesThe in service status as a result of topology processing. It indicates if the equipment is considered as energized by the power flow. It reflects if the equipment is connected within a solvable island. It does not necessarily reflect whether or not the island was solved by the power flow.
The individual phase status. If the attribute is unspecified, then three phase model is assumed.
Same definition as PowerElectronicsConnectionPhase.phaseUsed in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
Specifies the regulation status of the equipment. True is regulating, false is not regulating.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Maximum fault current this device will contribute, in per-unit of rated current, before the converter protection will trip or bypass.
nan
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Maximum reactive power limit. This is the maximum (nameplate) limit for the unit.
Same definition as PowerElectronicsConnectionPhase.qMinimum reactive power limit for the unit. This is the minimum (nameplate) limit for the unit.
Same definition as PowerElectronicsConnectionPhase.qActive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
Equivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909.
nan
Zero sequence resistance of the synchronous machine.
Same definition as PowerElectronicsConnection.rNameplate apparent power rating for the unit.
The attribute shall have a positive value.
nan
Rated voltage (nameplate data, Ur in IEC 60909-0). It is primarily used for short circuit data exchange according to IEC 60909.
The attribute shall be a positive value.
nan
Negative sequence Thevenin resistance.
Same definition as PowerElectronicsConnection.rPositive sequence Thevenin reactance.
nan
Zero sequence Thevenin reactance.
Same definition as PowerElectronicsConnection.xNegative sequence Thevenin reactance.
Same definition as PowerElectronicsConnection.xThe aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Hash table of StaticVarCompensator objects
No Additional PropertiesAll properties whose name matches the following regular expression must respect the following conditions
Property name regular expression:^.+$
A facility for providing variable and controllable shunt reactive power. The SVC typically consists of a stepdown transformer, filter, thyristor-controlled reactor, and thyristor-switched capacitor arms.
The SVC may operate in fixed MVar output mode or in voltage control mode. When in voltage control mode, the output of the SVC will be proportional to the deviation of voltage at the controlled bus from the voltage setpoint. The SVC characteristic slope defines the proportion. If the voltage at the controlled bus is equal to the voltage setpoint, the SVC MVar output is zero.
Pointer to Location object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
SVC control mode.
The reactive power output of the SVC is proportional to the difference between the voltage at the regulated bus and the voltage setpoint. When the regulated bus voltage is equal to the voltage setpoint, the reactive power output is zero.
Same definition as PowerElectronicsConnection.ratedUThe aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the regulation status of the equipment. True is regulating, false is not regulating.
Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
Capacitive reactance at maximum capacitive reactive power. Shall always be positive.
Same definition as PowerElectronicsConnection.xInductive reactance at maximum inductive reactive power. Shall always be negative.
Same definition as PowerElectronicsConnection.xThe characteristics slope of an SVC defines how the reactive power output changes in proportion to the difference between the regulated bus voltage and the voltage setpoint.
The attribute shall be a positive value or zero.
nan
Hash table of ExternalNetworkInjection objects
No Additional PropertiesAll properties whose name matches the following regular expression must respect the following conditions
Property name regular expression:^.+$
This class represents the external network and it is used for IEC 60909 calculations.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
Power Frequency Bias. This is the change in power injection divided by the change in frequency and negated. A positive value of the power frequency bias provides additional power injection upon a drop in frequency.
nan
Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik"). Used only if short circuit calculations are done according to superposition method.
Maximum initial symmetrical short-circuit currents (Ik" max) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909.
nan
Maximum active power of the injection.
Same definition as PowerElectronicsUnit.maxPMaximum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.
Same definition as PowerElectronicsConnectionPhase.qMaximum ratio of zero sequence resistance of Network Feeder to its zero sequence reactance (R(0)/X(0) max). Used for short circuit data exchange according to IEC 60909.
Maximum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) max). Used for short circuit data exchange according to IEC 60909.
Maximum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) max). Used for short circuit data exchange according to IEC 60909.
Minimum initial symmetrical short-circuit currents (Ik" min) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909.
Same definition as ExternalNetworkInjection.maxInitialSymShCCurrentMinimum active power of the injection.
Same definition as PowerElectronicsUnit.maxPMinimum reactive power limit. It is used for modelling of infeed for load flow exchange and not for short circuit modelling.
Same definition as PowerElectronicsConnectionPhase.qIndicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik"). Used for short circuit data exchange according to IEC 6090.
Minimum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) min). Used for short circuit data exchange according to IEC 60909.
Minimum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) min). Used for short circuit data exchange according to IEC 60909.
Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on.
Voltage factor in pu, which was used to calculate short-circuit current Ik" and power Sk". Used only if short circuit calculations are done according to superposition method.
Same definition as PowerElectronicsConnection.maxIFaultUsed in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
Specifies the regulation status of the equipment. True is regulating, false is not regulating.
Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for steady state solutions.
Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for steady state solutions.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Hash table of FrequencyConverter objects
No Additional PropertiesAll properties whose name matches the following regular expression must respect the following conditions
Property name regular expression:^.+$
A device to convert from one frequency to another (e.g., frequency F1 to F2) comprises a pair of FrequencyConverter instances. One converts from F1 to DC, the other converts the DC to F2.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the regulation status of the equipment. True is regulating, false is not regulating.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Frequency on the AC side.
nan
The maximum active power on the DC side at which the frequency converter should operate.
Same definition as PowerElectronicsUnit.maxPThe maximum voltage on the DC side at which the frequency converter should operate.
Same definition as PowerElectronicsConnection.ratedUThe minimum active power on the DC side at which the frequency converter should operate.
Same definition as PowerElectronicsUnit.maxPThe minimum voltage on the DC side at which the frequency converter should operate.
Same definition as PowerElectronicsConnection.ratedUHash table of ShuntCompensator objects
No Additional PropertiesAll properties whose name matches the following regular expression must respect the following conditions
Property name regular expression:^.+$
A shunt capacitor or reactor or switchable bank of shunt capacitors or reactors. A section of a shunt compensator is an individual capacitor or reactor. A negative value for bPerSection indicates that the compensator is a reactor. ShuntCompensator is a single terminal device. Ground is implied.
A shunt capacitor or reactor or switchable bank of shunt capacitors or reactors. A section of a shunt compensator is an individual capacitor or reactor. A negative value for bPerSection indicates that the compensator is a reactor. ShuntCompensator is a single terminal device. Ground is implied.
Same definition as ShuntCompensatorA linear shunt compensator has banks or sections with equal admittance values.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
Array of LinearShuntCompensatorPhase objects
No Additional ItemsA per phase linear shunt compensator has banks or sections with equal admittance values.
No Additional PropertiesThe maximum number of sections that may be switched in for this phase.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
For the capacitor phase, the normal number of sections switched in. The value shall be between zero and ShuntCompensatorPhase.maximumSections.
Phase of this shunt compensator component. If the shunt compensator is wye connected, the connection is from the indicated phase to the central ground or neutral point. If the shunt compensator is delta connected, the phase indicates a shunt compensator connected from the indicated phase to the next logical non-neutral phase.
Same definition as PowerElectronicsConnectionPhase.phaseShunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed, a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input.
For LinearShuntConpensator the value shall be between zero and ShuntCompensatorPhase.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of non-integer values.
For NonlinearShuntCompensator-s shall only be set to one of the NonlinearShuntCompenstorPhasePoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPhasePoint-s.
Conductance per section for this phase if shunt compensator is wye connected. Conductance per section phase to phase if shunt compensator is delta connected.
nan
Susceptance per section of the phase if shunt compensator is wye connected. Susceptance per section phase to phase if shunt compensator is delta connected.
nan
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Pointer to ShuntCompensatorInfo object
Array of SvShuntCompensatorSections objects
No Additional ItemsState variable for the number of sections in service for a shunt compensator.
No Additional PropertiesThe number of sections in service as a continuous variable. The attribute shall be a positive value or zero. To get integer value scale with ShuntCompensator.bPerSection.
The terminal phase at which the connection is applied. If missing, the injection is assumed to be balanced among non-neutral phases.
Same definition as PowerElectronicsConnectionPhase.phasePointer to SwitchingAction object
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
Specifies the regulation status of the equipment. True is regulating, false is not regulating.
Zero sequence shunt (charging) susceptance per section.
Same definition as LinearShuntCompensatorPhase.bPerSectionShunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed, a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input.
For LinearShuntConpensator the value shall be between zero and ShuntCompensator.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of non-integer values.
For NonlinearShuntCompensator-s shall only be set to one of the NonlinearShuntCompenstorPoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPoint-s.
Positive sequence shunt (charging) susceptance per section.
Same definition as LinearShuntCompensatorPhase.bPerSectionZero sequence shunt (charging) conductance per section.
Same definition as LinearShuntCompensatorPhase.gPerSectionPositive sequence shunt (charging) conductance per section.
Same definition as LinearShuntCompensatorPhase.gPerSectionAn automatic voltage regulation delay (AVRDelay) which is the time delay from a change in voltage to when the capacitor is allowed to change state. This filters out temporary changes in voltage.
Time, in seconds
Used for Yn and Zn connections. True if the neutral is solidly grounded.
The maximum number of sections that may be switched in.
The voltage at which the nominal reactive power may be calculated. This should normally be within 10% of the voltage at which the capacitor is connected to the network.
Same definition as PowerElectronicsConnection.ratedUThe normal number of sections switched in. The value shall be between zero and ShuntCompensator.maximumSections.
The type of phase connection, such as wye or delta.
The switch on count since the capacitor count was last reset or initialized.
The date and time when the capacitor bank was last switched on.
Voltage sensitivity required for the device to regulate the bus voltage, in voltage/reactive power.
Same definition as StaticVarCompensator.slopeThe equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
A non linear shunt compensator has bank or section admittance values that differ. The attributes g, b, g0 and b0 of the associated NonlinearShuntCompensatorPoint describe the total conductance and admittance of a NonlinearShuntCompensatorPoint at a section number specified by NonlinearShuntCompensatorPoint.sectionNumber.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
Array of NonlinearShuntCompensatorPhase objects
No Additional ItemsA per phase non linear shunt compensator has bank or section admittance values that differ. The attributes g and b of the associated NonlinearShuntCompensatorPhasePoint describe the total conductance and admittance of a NonlinearShuntCompensatorPhasePoint at a section number specified by NonlinearShuntCompensatorPhasePoint.sectionNumber.
No Additional PropertiesThe maximum number of sections that may be switched in for this phase.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
For the capacitor phase, the normal number of sections switched in. The value shall be between zero and ShuntCompensatorPhase.maximumSections.
Phase of this shunt compensator component. If the shunt compensator is wye connected, the connection is from the indicated phase to the central ground or neutral point. If the shunt compensator is delta connected, the phase indicates a shunt compensator connected from the indicated phase to the next logical non-neutral phase.
Same definition as PowerElectronicsConnectionPhase.phaseShunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed, a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input.
For LinearShuntConpensator the value shall be between zero and ShuntCompensatorPhase.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of non-integer values.
For NonlinearShuntCompensator-s shall only be set to one of the NonlinearShuntCompenstorPhasePoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPhasePoint-s.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Pointer to ShuntCompensatorInfo object
Array of SvShuntCompensatorSections objects
Same definition as ShuntCompensator.SvShuntCompensatorSectionsPointer to SwitchingAction object
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
Specifies the regulation status of the equipment. True is regulating, false is not regulating.
Shunt compensator sections in use. Starting value for steady state solution. The attribute shall be a positive value or zero. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed, a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input.
For LinearShuntConpensator the value shall be between zero and ShuntCompensator.maximumSections. At value zero the shunt compensator conductance and admittance is zero. Linear interpolation of conductance and admittance between the previous and next integer section is applied in case of non-integer values.
For NonlinearShuntCompensator-s shall only be set to one of the NonlinearShuntCompenstorPoint.sectionNumber. There is no interpolation between NonlinearShuntCompenstorPoint-s.
An automatic voltage regulation delay (AVRDelay) which is the time delay from a change in voltage to when the capacitor is allowed to change state. This filters out temporary changes in voltage.
Same definition as ShuntCompensator.aVRDelayUsed for Yn and Zn connections. True if the neutral is solidly grounded.
The maximum number of sections that may be switched in.
The voltage at which the nominal reactive power may be calculated. This should normally be within 10% of the voltage at which the capacitor is connected to the network.
Same definition as PowerElectronicsConnection.ratedUThe normal number of sections switched in. The value shall be between zero and ShuntCompensator.maximumSections.
The type of phase connection, such as wye or delta.
Same definition as ShuntCompensator.phaseConnectionThe switch on count since the capacitor count was last reset or initialized.
The date and time when the capacitor bank was last switched on.
Voltage sensitivity required for the device to regulate the bus voltage, in voltage/reactive power.
Same definition as StaticVarCompensator.slopeThe equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Hash table of RotatingMachine objects
No Additional PropertiesAll properties whose name matches the following regular expression must respect the following conditions
Property name regular expression:^.+$
A rotating machine which may be used as a generator or motor.
A rotating machine which may be used as a generator or motor.
Same definition as RotatingMachineAn electromechanical device that operates with shaft rotating synchronously with the network. It is a single machine operating either as a generator or synchronous condenser or pump.
No Additional Propertiesnan
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
A single or set of synchronous machines for converting mechanical power into alternating-current power. For example, individual machines within a set may be defined for scheduling purposes while a single control signal is derived for the set. In this case there would be a GeneratingUnit for each member of the set and an additional GeneratingUnit corresponding to the set.
A generating unit whose prime mover is a hydraulic turbine (e.g., Francis, Pelton, Kaplan).
No Additional PropertiesThe generating unit's Operator-approved current operating schedule (or plan), typically produced with the aid of unit commitment type analyses. The X-axis represents absolute time. The Y1-axis represents the status (0=off-line and unavailable: 1=available: 2=must run: 3=must run at fixed power value: etc.). The Y2-axis represents the must run fixed power value where required.
No Additional PropertiesThe aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The time between each pair of subsequent regular time points in sequence order.
Same definition as ShuntCompensator.aVRDelayThe time for the first time point. The value can be a time of day, not a specific date.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The time for the last time point. The value can be a time of day, not a specific date.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Array of GenUnitOpCostCurve objects
No Additional ItemsRelationship between unit operating cost (Y-axis) and unit output active power (X-axis). The operating cost curve for thermal units is derived from heat input and fuel costs. The operating cost curve for hydro units is derived from water flow rates and equivalent water costs.
No Additional PropertiesFlag is set to true when output is expressed in net active power.
The style or shape of the curve.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Governor motor position limit.
Same definition as PowerElectronicsConnection.maxIFaultGovernor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency.
Same definition as InefficientBatteryUnit.efficiencyDischargeType of turbine.
The height water drops from the reservoir mid-point to the turbine.
nan
High limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPLow limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPGenerating unit long term economic participation factor.
Maximum high economic active power limit, that should not exceed the maximum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMaximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.
Same definition as PowerElectronicsUnit.maxPThis is the maximum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPDefault initial active power which is used to store a powerflow result for the initial active power for this unit in this network configuration.
Same definition as PowerElectronicsUnit.maxPMinimum time interval between unit shutdown and startup.
Same definition as ShuntCompensator.aVRDelayThis is the minimum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPDetail level of the generator model data.
nan
The nominal power of the generating unit. Used to give precise meaning to percentage based attributes such as the governor speed change droop (governorSCD attribute).
The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.
Generating unit economic participation factor. The sum of the participation factors across generating units does not have to sum to one. It is used for representing distributed slack participation factor. The attribute shall be a positive value or zero.
Defined as: 1 / ( 1 - Incremental Transmission Loss); with the Incremental Transmission Loss expressed as a plus or minus value. The typical range of penalty factors is (0.9 to 1.1).
The normal maximum rate the generating unit active power output can be raised by control actions.
nan
The unit's gross rated maximum capacity (book value).
The attribute shall be a positive value.
The gross rated minimum generation level which the unit can safely operate at while delivering power to the transmission grid.
The attribute shall be a positive value.
The net rated maximum capacity determined by subtracting the auxiliary power used to operate the internal plant machinery from the rated gross maximum capacity.
The attribute shall be a positive value.
The normal maximum rate the generating unit active power output can be lowered by control actions.
Same definition as GeneratingUnit.raiseRampRateGenerating unit short term economic participation factor.
The initial startup cost incurred for each start of the GeneratingUnit.
nan
nan
Time it takes to get the unit on-line, from the time that the prime mover mechanical power is applied.
Same definition as ShuntCompensator.aVRDelayGenerating unit economic participation factor.
The variable cost component of production per unit of ActivePower.
Same definition as GeneratingUnit.startupCostThe description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
Energy conversion capability for generating.
The equivalent cost of water that drives the hydro turbine.
nan
Low economic active power limit that shall be greater than or equal to the minimum operating active power limit.
Same definition as PowerElectronicsUnit.maxPThe aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The efficiency of the unit in converting the fuel into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeSpecifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The planned unused capacity (spinning reserve) which can be used to support emergency load.
Same definition as PowerElectronicsUnit.maxPThe planned unused capacity which can be used to support automatic control overruns.
Same definition as PowerElectronicsUnit.maxPFor dispatchable units, this value represents the economic active power basepoint, for units that are not dispatchable, this value represents the fixed generation value. The value shall be between the operating low and high limits.
Same definition as PowerElectronicsUnit.maxPUnit control error deadband. When a unit's desired active power change is less than this deadband, then no control pulses will be sent to the unit.
Same definition as PowerElectronicsUnit.maxPPulse high limit which is the largest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayPulse low limit which is the smallest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayUnit response rate which specifies the active power change for a control pulse of one second in the most responsive loading level of the unit.
Same definition as GeneratingUnit.raiseRampRateThe efficiency of the unit in converting mechanical energy, from the prime mover, into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeThe aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
The unit control mode.
The source of controls for a generating unit. Defines the control status of the generating unit.
A solar thermal generating unit, connected to the grid by means of a rotating machine. This class does not represent photovoltaic (PV) generation.
No Additional PropertiesThe generating unit's Operator-approved current operating schedule (or plan), typically produced with the aid of unit commitment type analyses. The X-axis represents absolute time. The Y1-axis represents the status (0=off-line and unavailable: 1=available: 2=must run: 3=must run at fixed power value: etc.). The Y2-axis represents the must run fixed power value where required.
Same definition as GeneratingUnit.GenUnitOpScheduleArray of GenUnitOpCostCurve objects
Same definition as GeneratingUnit.GenUnitOpCostCurvesGovernor motor position limit.
Same definition as PowerElectronicsConnection.maxIFaultGovernor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency.
Same definition as InefficientBatteryUnit.efficiencyDischargeHigh limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPDefault initial active power which is used to store a powerflow result for the initial active power for this unit in this network configuration.
Same definition as PowerElectronicsUnit.maxPGenerating unit long term economic participation factor.
Low limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPThe normal maximum rate the generating unit active power output can be lowered by control actions.
Same definition as GeneratingUnit.raiseRampRateMaximum high economic active power limit, that should not exceed the maximum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMaximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.
Same definition as PowerElectronicsUnit.maxPThis is the maximum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPLow economic active power limit that shall be greater than or equal to the minimum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMinimum time interval between unit shutdown and startup.
Same definition as ShuntCompensator.aVRDelayThis is the minimum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPDetail level of the generator model data.
Same definition as GeneratingUnit.modelDetailThe nominal power of the generating unit. Used to give precise meaning to percentage based attributes such as the governor speed change droop (governorSCD attribute).
The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.
Generating unit economic participation factor. The sum of the participation factors across generating units does not have to sum to one. It is used for representing distributed slack participation factor. The attribute shall be a positive value or zero.
Defined as: 1 / ( 1 - Incremental Transmission Loss); with the Incremental Transmission Loss expressed as a plus or minus value. The typical range of penalty factors is (0.9 to 1.1).
The normal maximum rate the generating unit active power output can be raised by control actions.
Same definition as GeneratingUnit.raiseRampRateThe unit's gross rated maximum capacity (book value).
The attribute shall be a positive value.
The gross rated minimum generation level which the unit can safely operate at while delivering power to the transmission grid.
The attribute shall be a positive value.
The net rated maximum capacity determined by subtracting the auxiliary power used to operate the internal plant machinery from the rated gross maximum capacity.
The attribute shall be a positive value.
Generating unit short term economic participation factor.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The initial startup cost incurred for each start of the GeneratingUnit.
Same definition as GeneratingUnit.startupCostTime it takes to get the unit on-line, from the time that the prime mover mechanical power is applied.
Same definition as ShuntCompensator.aVRDelayGenerating unit economic participation factor.
The variable cost component of production per unit of ActivePower.
Same definition as GeneratingUnit.startupCostThe description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The efficiency of the unit in converting the fuel into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeSpecifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The planned unused capacity (spinning reserve) which can be used to support emergency load.
Same definition as PowerElectronicsUnit.maxPThe planned unused capacity which can be used to support automatic control overruns.
Same definition as PowerElectronicsUnit.maxPFor dispatchable units, this value represents the economic active power basepoint, for units that are not dispatchable, this value represents the fixed generation value. The value shall be between the operating low and high limits.
Same definition as PowerElectronicsUnit.maxPUnit control error deadband. When a unit's desired active power change is less than this deadband, then no control pulses will be sent to the unit.
Same definition as PowerElectronicsUnit.maxPPulse high limit which is the largest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayPulse low limit which is the smallest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayUnit response rate which specifies the active power change for a control pulse of one second in the most responsive loading level of the unit.
Same definition as GeneratingUnit.raiseRampRateThe efficiency of the unit in converting mechanical energy, from the prime mover, into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeThe aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
The source of controls for a generating unit. Defines the control status of the generating unit.
Same definition as GeneratingUnit.genControlSourceA nuclear generating unit.
No Additional PropertiesThe generating unit's Operator-approved current operating schedule (or plan), typically produced with the aid of unit commitment type analyses. The X-axis represents absolute time. The Y1-axis represents the status (0=off-line and unavailable: 1=available: 2=must run: 3=must run at fixed power value: etc.). The Y2-axis represents the must run fixed power value where required.
Same definition as GeneratingUnit.GenUnitOpScheduleArray of GenUnitOpCostCurve objects
Same definition as GeneratingUnit.GenUnitOpCostCurvesGovernor motor position limit.
Same definition as PowerElectronicsConnection.maxIFaultGovernor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency.
Same definition as InefficientBatteryUnit.efficiencyDischargeHigh limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPDefault initial active power which is used to store a powerflow result for the initial active power for this unit in this network configuration.
Same definition as PowerElectronicsUnit.maxPGenerating unit long term economic participation factor.
Low limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPThe normal maximum rate the generating unit active power output can be lowered by control actions.
Same definition as GeneratingUnit.raiseRampRateMaximum high economic active power limit, that should not exceed the maximum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMaximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.
Same definition as PowerElectronicsUnit.maxPThis is the maximum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPLow economic active power limit that shall be greater than or equal to the minimum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMinimum time interval between unit shutdown and startup.
Same definition as ShuntCompensator.aVRDelayThis is the minimum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPDetail level of the generator model data.
Same definition as GeneratingUnit.modelDetailThe nominal power of the generating unit. Used to give precise meaning to percentage based attributes such as the governor speed change droop (governorSCD attribute).
The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.
Generating unit economic participation factor. The sum of the participation factors across generating units does not have to sum to one. It is used for representing distributed slack participation factor. The attribute shall be a positive value or zero.
Defined as: 1 / ( 1 - Incremental Transmission Loss); with the Incremental Transmission Loss expressed as a plus or minus value. The typical range of penalty factors is (0.9 to 1.1).
The normal maximum rate the generating unit active power output can be raised by control actions.
Same definition as GeneratingUnit.raiseRampRateThe unit's gross rated maximum capacity (book value).
The attribute shall be a positive value.
The gross rated minimum generation level which the unit can safely operate at while delivering power to the transmission grid.
The attribute shall be a positive value.
The net rated maximum capacity determined by subtracting the auxiliary power used to operate the internal plant machinery from the rated gross maximum capacity.
The attribute shall be a positive value.
Generating unit short term economic participation factor.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The initial startup cost incurred for each start of the GeneratingUnit.
Same definition as GeneratingUnit.startupCostTime it takes to get the unit on-line, from the time that the prime mover mechanical power is applied.
Same definition as ShuntCompensator.aVRDelayGenerating unit economic participation factor.
The variable cost component of production per unit of ActivePower.
Same definition as GeneratingUnit.startupCostThe description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The efficiency of the unit in converting the fuel into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeSpecifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The planned unused capacity (spinning reserve) which can be used to support emergency load.
Same definition as PowerElectronicsUnit.maxPThe planned unused capacity which can be used to support automatic control overruns.
Same definition as PowerElectronicsUnit.maxPFor dispatchable units, this value represents the economic active power basepoint, for units that are not dispatchable, this value represents the fixed generation value. The value shall be between the operating low and high limits.
Same definition as PowerElectronicsUnit.maxPUnit control error deadband. When a unit's desired active power change is less than this deadband, then no control pulses will be sent to the unit.
Same definition as PowerElectronicsUnit.maxPPulse high limit which is the largest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayPulse low limit which is the smallest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayUnit response rate which specifies the active power change for a control pulse of one second in the most responsive loading level of the unit.
Same definition as GeneratingUnit.raiseRampRateThe efficiency of the unit in converting mechanical energy, from the prime mover, into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeThe aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
The source of controls for a generating unit. Defines the control status of the generating unit.
Same definition as GeneratingUnit.genControlSourceA wind driven generating unit, connected to the grid by means of a rotating machine. May be used to represent a single turbine or an aggregation.
No Additional PropertiesThe generating unit's Operator-approved current operating schedule (or plan), typically produced with the aid of unit commitment type analyses. The X-axis represents absolute time. The Y1-axis represents the status (0=off-line and unavailable: 1=available: 2=must run: 3=must run at fixed power value: etc.). The Y2-axis represents the must run fixed power value where required.
Same definition as GeneratingUnit.GenUnitOpScheduleArray of GenUnitOpCostCurve objects
Same definition as GeneratingUnit.GenUnitOpCostCurvesGovernor motor position limit.
Same definition as PowerElectronicsConnection.maxIFaultGovernor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency.
Same definition as InefficientBatteryUnit.efficiencyDischargeHigh limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPDefault initial active power which is used to store a powerflow result for the initial active power for this unit in this network configuration.
Same definition as PowerElectronicsUnit.maxPGenerating unit long term economic participation factor.
Low limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPThe normal maximum rate the generating unit active power output can be lowered by control actions.
Same definition as GeneratingUnit.raiseRampRateMaximum high economic active power limit, that should not exceed the maximum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMaximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.
Same definition as PowerElectronicsUnit.maxPThis is the maximum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPLow economic active power limit that shall be greater than or equal to the minimum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMinimum time interval between unit shutdown and startup.
Same definition as ShuntCompensator.aVRDelayThis is the minimum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPDetail level of the generator model data.
Same definition as GeneratingUnit.modelDetailThe nominal power of the generating unit. Used to give precise meaning to percentage based attributes such as the governor speed change droop (governorSCD attribute).
The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.
Generating unit economic participation factor. The sum of the participation factors across generating units does not have to sum to one. It is used for representing distributed slack participation factor. The attribute shall be a positive value or zero.
Defined as: 1 / ( 1 - Incremental Transmission Loss); with the Incremental Transmission Loss expressed as a plus or minus value. The typical range of penalty factors is (0.9 to 1.1).
The normal maximum rate the generating unit active power output can be raised by control actions.
Same definition as GeneratingUnit.raiseRampRateThe unit's gross rated maximum capacity (book value).
The attribute shall be a positive value.
The gross rated minimum generation level which the unit can safely operate at while delivering power to the transmission grid.
The attribute shall be a positive value.
The net rated maximum capacity determined by subtracting the auxiliary power used to operate the internal plant machinery from the rated gross maximum capacity.
The attribute shall be a positive value.
Generating unit short term economic participation factor.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The initial startup cost incurred for each start of the GeneratingUnit.
Same definition as GeneratingUnit.startupCostTime it takes to get the unit on-line, from the time that the prime mover mechanical power is applied.
Same definition as ShuntCompensator.aVRDelayGenerating unit economic participation factor.
The variable cost component of production per unit of ActivePower.
Same definition as GeneratingUnit.startupCostThe description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The efficiency of the unit in converting the fuel into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeSpecifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The kind of wind generating unit.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The planned unused capacity (spinning reserve) which can be used to support emergency load.
Same definition as PowerElectronicsUnit.maxPThe planned unused capacity which can be used to support automatic control overruns.
Same definition as PowerElectronicsUnit.maxPFor dispatchable units, this value represents the economic active power basepoint, for units that are not dispatchable, this value represents the fixed generation value. The value shall be between the operating low and high limits.
Same definition as PowerElectronicsUnit.maxPUnit control error deadband. When a unit's desired active power change is less than this deadband, then no control pulses will be sent to the unit.
Same definition as PowerElectronicsUnit.maxPPulse high limit which is the largest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayPulse low limit which is the smallest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayUnit response rate which specifies the active power change for a control pulse of one second in the most responsive loading level of the unit.
Same definition as GeneratingUnit.raiseRampRateThe efficiency of the unit in converting mechanical energy, from the prime mover, into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeThe aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
The source of controls for a generating unit. Defines the control status of the generating unit.
Same definition as GeneratingUnit.genControlSourceA generating unit whose prime mover could be a steam turbine, combustion turbine, or diesel engine.
No Additional PropertiesThe generating unit's Operator-approved current operating schedule (or plan), typically produced with the aid of unit commitment type analyses. The X-axis represents absolute time. The Y1-axis represents the status (0=off-line and unavailable: 1=available: 2=must run: 3=must run at fixed power value: etc.). The Y2-axis represents the must run fixed power value where required.
Same definition as GeneratingUnit.GenUnitOpScheduleArray of GenUnitOpCostCurve objects
Same definition as GeneratingUnit.GenUnitOpCostCurvesGovernor motor position limit.
Same definition as PowerElectronicsConnection.maxIFaultGovernor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency.
Same definition as InefficientBatteryUnit.efficiencyDischargeHigh limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPDefault initial active power which is used to store a powerflow result for the initial active power for this unit in this network configuration.
Same definition as PowerElectronicsUnit.maxPGenerating unit long term economic participation factor.
Low limit for secondary (AGC) control.
Same definition as PowerElectronicsUnit.maxPThe normal maximum rate the generating unit active power output can be lowered by control actions.
Same definition as GeneratingUnit.raiseRampRateMaximum high economic active power limit, that should not exceed the maximum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMaximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.
Same definition as PowerElectronicsUnit.maxPThis is the maximum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPLow economic active power limit that shall be greater than or equal to the minimum operating active power limit.
Same definition as PowerElectronicsUnit.maxPMinimum time interval between unit shutdown and startup.
Same definition as ShuntCompensator.aVRDelayThis is the minimum operating active power limit the dispatcher can enter for this unit.
Same definition as PowerElectronicsUnit.maxPDetail level of the generator model data.
Same definition as GeneratingUnit.modelDetailThe nominal power of the generating unit. Used to give precise meaning to percentage based attributes such as the governor speed change droop (governorSCD attribute).
The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.
Generating unit economic participation factor. The sum of the participation factors across generating units does not have to sum to one. It is used for representing distributed slack participation factor. The attribute shall be a positive value or zero.
Defined as: 1 / ( 1 - Incremental Transmission Loss); with the Incremental Transmission Loss expressed as a plus or minus value. The typical range of penalty factors is (0.9 to 1.1).
The normal maximum rate the generating unit active power output can be raised by control actions.
Same definition as GeneratingUnit.raiseRampRateThe unit's gross rated maximum capacity (book value).
The attribute shall be a positive value.
The gross rated minimum generation level which the unit can safely operate at while delivering power to the transmission grid.
The attribute shall be a positive value.
The net rated maximum capacity determined by subtracting the auxiliary power used to operate the internal plant machinery from the rated gross maximum capacity.
The attribute shall be a positive value.
Generating unit short term economic participation factor.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The initial startup cost incurred for each start of the GeneratingUnit.
Same definition as GeneratingUnit.startupCostTime it takes to get the unit on-line, from the time that the prime mover mechanical power is applied.
Same definition as ShuntCompensator.aVRDelayGenerating unit economic participation factor.
The variable cost component of production per unit of ActivePower.
Same definition as GeneratingUnit.startupCostThe description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
The efficiency of the unit in converting the fuel into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeSpecifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Operating and maintenance cost for the thermal unit.
nan
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The planned unused capacity (spinning reserve) which can be used to support emergency load.
Same definition as PowerElectronicsUnit.maxPThe planned unused capacity which can be used to support automatic control overruns.
Same definition as PowerElectronicsUnit.maxPFor dispatchable units, this value represents the economic active power basepoint, for units that are not dispatchable, this value represents the fixed generation value. The value shall be between the operating low and high limits.
Same definition as PowerElectronicsUnit.maxPUnit control error deadband. When a unit's desired active power change is less than this deadband, then no control pulses will be sent to the unit.
Same definition as PowerElectronicsUnit.maxPPulse high limit which is the largest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayPulse low limit which is the smallest control pulse that the unit can respond to.
Same definition as ShuntCompensator.aVRDelayUnit response rate which specifies the active power change for a control pulse of one second in the most responsive loading level of the unit.
Same definition as GeneratingUnit.raiseRampRateThe efficiency of the unit in converting mechanical energy, from the prime mover, into electrical energy.
Same definition as InefficientBatteryUnit.efficiencyDischargeThe aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
The source of controls for a generating unit. Defines the control status of the generating unit.
Same definition as GeneratingUnit.genControlSourcePointer to BaseVoltage object
Steady-state short-circuit current (in A for the profile) of generator with compound excitation during 3-phase short circuit.
- Ikk=0: Generator with no compound excitation.
- Ikk<>0: Generator with compound excitation.
Ikk is used to calculate the minimum steady-state short-circuit current for generators with compound excitation.
(4.6.1.2 in IEC 60909-0:2001).
Used only for single fed short circuit on a generator. (4.3.4.2. in IEC 60909-0:2001).
Time delay required when switching from Manual to Automatic Voltage Regulation. This value is used in the accelerating power reference frame for powerflow solutions.
Same definition as ShuntCompensator.aVRDelayMaximum reactive power limit. This is the maximum (nameplate) limit for the unit.
Same definition as PowerElectronicsConnectionPhase.qMaximum voltage limit for the unit.
Same definition as PowerElectronicsConnection.ratedUMinimum reactive power limit for the unit.
Same definition as PowerElectronicsConnectionPhase.qMinimum voltage limit for the unit.
Same definition as PowerElectronicsConnection.ratedUFactor to calculate the breaking current (Section 4.5.2.1 in IEC 60909-0).
Used only for single fed short circuit on a generator (Section 4.3.4.2. in IEC 60909-0).
Current mode of operation.
Part of the coordinated reactive control that comes from this machine. The attribute is used as a participation factor not necessarily summing up to 100% for the participating devices in the control.
Same definition as InefficientBatteryUnit.efficiencyDischargeEquivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909.
Same definition as PowerElectronicsConnection.rZero sequence resistance of the synchronous machine.
Same definition as PowerElectronicsConnection.rNegative sequence resistance.
Same definition as PowerElectronicsConnection.rPriority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on.
Direct-axis subtransient reactance saturated, also known as Xd"sat.
Same definition as PowerElectronicsConnection.maxIFaultDirect-axes saturated synchronous reactance (xdsat); reciprocal of short-circuit ration. Used for short circuit data exchange, only for single fed short circuit on a generator. (4.3.4.2. in IEC 60909-0:2001).
Same definition as PowerElectronicsConnection.maxIFaultSaturated Direct-axis transient reactance. The attribute is primarily used for short circuit calculations according to ANSI.
Same definition as PowerElectronicsConnection.maxIFaultType of rotor, used by short circuit applications, only for single fed short circuit according to IEC 60909.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Modes that this synchronous machine can operate in.
Range of generator voltage regulation (PG in IEC 60909-0) used for calculation of the impedance correction factor KG defined in IEC 60909-0.
This attribute is used to describe the operating voltage of the generating unit.
Zero sequence reactance of the synchronous machine.
Same definition as PowerElectronicsConnection.xThe description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
Specifies the regulation status of the equipment. True is regulating, false is not regulating.
Power factor (nameplate data). It is primarily used for short circuit data exchange according to IEC 60909. The attribute cannot be a negative value.
Nameplate apparent power rating for the unit.
The attribute shall have a positive value.
Rated voltage (nameplate data, Ur in IEC 60909-0). It is primarily used for short circuit data exchange according to IEC 60909.
The attribute shall be a positive value.
Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Time delay required when switching from Automatic Voltage Regulation (AVR) to Manual for a lagging MVAr violation.
Same definition as ShuntCompensator.aVRDelayTime delay required when switching from Automatic Voltage Regulation (AVR) to Manual for a leading MVAr violation.
Same definition as ShuntCompensator.aVRDelayDefault base reactive power value. This value represents the initial reactive power that can be used by any application function.
Same definition as PowerElectronicsConnectionPhase.qActive power consumed when in condenser mode operation.
Same definition as PowerElectronicsUnit.maxPTemperature or pressure of coolant medium.
Method of cooling the machine.
Indicates whether or not the generator is earthed. Used for short circuit data exchange according to IEC 60909.
Generator star point earthing resistance (Re). Used for short circuit data exchange according to IEC 60909.
Same definition as PowerElectronicsConnection.rGenerator star point earthing reactance (Xe). Used for short circuit data exchange according to IEC 60909.
Same definition as PowerElectronicsConnection.xA rotating machine whose shaft rotates asynchronously with the electrical field. Also known as an induction machine with no external connection to the rotor windings, e.g. squirrel-cage induction machine.
No Additional PropertiesPointer to Location object
Pointer to SwitchingAction object
A single or set of synchronous machines for converting mechanical power into alternating-current power. For example, individual machines within a set may be defined for scheduling purposes while a single control signal is derived for the set. In this case there would be a GeneratingUnit for each member of the set and an additional GeneratingUnit corresponding to the set.
Same definition as RotatingMachine.GeneratingUnitPointer to BaseVoltage object
Indicates whether the machine is a converter fed drive. Used for short circuit data exchange according to IEC 60909.
Efficiency of the asynchronous machine at nominal operation as a percentage. Indicator for converter drive motors. Used for short circuit data exchange according to IEC 60909.
Same definition as InefficientBatteryUnit.efficiencyDischargeRatio of locked-rotor current to the rated current of the motor (Ia/Ir). Used for short circuit data exchange according to IEC 60909.
Nameplate data indicates if the machine is 50 Hz or 60 Hz.
Same definition as FrequencyConverter.frequencyNameplate data. Depends on the slip and number of pole pairs.
nan
Number of pole pairs of stator. Used for short circuit data exchange according to IEC 60909.
Rated mechanical power (Pr in IEC 60909-0). Used for short circuit data exchange according to IEC 60909.
Same definition as PowerElectronicsUnit.maxPIndicates for converter drive motors if the power can be reversible. Used for short circuit data exchange according to IEC 60909.
Locked rotor ratio (R/X). Used for short circuit data exchange according to IEC 60909.
Transient rotor time constant (greater than tppo).
Same definition as ShuntCompensator.aVRDelaySub-transient rotor time constant (greater than 0).
Same definition as ShuntCompensator.aVRDelayDamper 1 winding leakage reactance.
Same definition as PowerElectronicsConnection.xDamper 2 winding leakage reactance.
Same definition as PowerElectronicsConnection.xTransient reactance (unsaturated) (greater than or equal to xpp).
Same definition as PowerElectronicsConnection.xSub-transient reactance (unsaturated).
Same definition as PowerElectronicsConnection.xSynchronous reactance (greater than xp).
Same definition as PowerElectronicsConnection.xThe description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
Specifies the regulation status of the equipment. True is regulating, false is not regulating.
Power factor (nameplate data). It is primarily used for short circuit data exchange according to IEC 60909. The attribute cannot be a negative value.
Nameplate apparent power rating for the unit.
The attribute shall have a positive value.
Rated voltage (nameplate data, Ur in IEC 60909-0). It is primarily used for short circuit data exchange according to IEC 60909.
The attribute shall be a positive value.
Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Indicates the type of Asynchronous Machine (motor or generator).
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Hash table of EnergyConsumer objects
No Additional PropertiesAll properties whose name matches the following regular expression must respect the following conditions
Property name regular expression:^.+$
Generic user of energy - a point of consumption on the power system model.
EnergyConsumer.pfixed, .qfixed, .pfixedPct and .qfixedPct have meaning only if there is no LoadResponseCharacteristic associated with EnergyConsumer or if LoadResponseCharacteristic.exponentModel is set to False.
Generic user of energy - a point of consumption on the power system model.
EnergyConsumer.pfixed, .qfixed, .pfixedPct and .qfixedPct have meaning only if there is no LoadResponseCharacteristic associated with EnergyConsumer or if LoadResponseCharacteristic.exponentModel is set to False.
ConformLoad represent loads that follow a daily load change pattern where the pattern can be used to scale the load with a system load.
No Additional PropertiesPointer to EnergyConsumerSchedule object
Pointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to LoadResponseCharacteristic object
Pointer to BaseVoltage object
Array of EnergyConsumerPhase objects
No Additional ItemsA single phase of an energy consumer.
No Additional PropertiesActive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
Active power of the load that is a fixed quantity. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as PowerElectronicsUnit.maxPFixed active power as per cent of load group fixed active power. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as InefficientBatteryUnit.efficiencyDischargePhase of this energy consumer component. If the energy consumer is wye connected, the connection is from the indicated phase to the central ground or neutral point. If the energy consumer is delta connected, the phase indicates an energy consumer connected from the indicated phase to the next logical non-neutral phase.
Same definition as PowerElectronicsConnectionPhase.phaseReactive power of the load that is a fixed quantity. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as PowerElectronicsConnectionPhase.qFixed reactive power as per cent of load group fixed reactive power. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as InefficientBatteryUnit.efficiencyDischargeReactive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Fixed reactive power as a percentage of load group fixed reactive power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as InefficientBatteryUnit.efficiencyDischargeActive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Number of individual customers represented by this demand.
Used for Yn and Zn connections. True if the neutral is solidly grounded.
Active power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as PowerElectronicsUnit.maxPFixed active power as a percentage of load group fixed active power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as InefficientBatteryUnit.efficiencyDischargeThe type of phase connection, such as wye or delta.
Same definition as ShuntCompensator.phaseConnectionReactive power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as PowerElectronicsConnectionPhase.qReactive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
NonConformLoad represents loads that do not follow a daily load change pattern and whose changes are not correlated with the daily load change pattern.
No Additional PropertiesPointer to EnergyConsumerSchedule object
Pointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to LoadResponseCharacteristic object
Pointer to BaseVoltage object
Array of EnergyConsumerPhase objects
Same definition as EnergyConsumer.EnergyConsumerPhaseFixed reactive power as a percentage of load group fixed reactive power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as InefficientBatteryUnit.efficiencyDischargeActive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Number of individual customers represented by this demand.
Used for Yn and Zn connections. True if the neutral is solidly grounded.
Active power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as PowerElectronicsUnit.maxPFixed active power as a percentage of load group fixed active power. Used to represent the time-varying components. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as InefficientBatteryUnit.efficiencyDischargeThe type of phase connection, such as wye or delta.
Same definition as ShuntCompensator.phaseConnectionReactive power of the load that is a fixed quantity and does not vary as load group value varies. Load sign convention is used, i.e. positive sign means flow out from a node.
Same definition as PowerElectronicsConnectionPhase.qReactive power of the load. Load sign convention is used, i.e. positive sign means flow out from a node.
For voltage dependent loads the value is at rated voltage.
Starting value for a steady state solution.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
Hash table of EnergySource objects
No Additional PropertiesAll properties whose name matches the following regular expression must respect the following conditions
Property name regular expression:^.+$
A generic equivalent for an energy supplier on a transmission or distribution voltage level.
No Additional PropertiesPointer to EquipmentContainer object
Pointer to Curve object
Pointer to Location object
Pointer to SwitchingAction object
Pointer to SwitchingAction object
Pointer to BaseVoltage object
Array of EnergySourcePhase objects
No Additional ItemsRepresents the single phase information of an unbalanced energy source.
No Additional PropertiesUsed in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
Phase of this energy source component. If the energy source wye connected, the connection is from the indicated phase to the central ground or neutral point. If the energy source is delta connected, the phase indicates an energy source connected from the indicated phase to the next logical non-neutral phase.
Same definition as PowerElectronicsConnectionPhase.phaseThe description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.
This is the minimum active power that can be produced by the source. Load sign convention is used, i.e. positive sign means flow out from a TopologicalNode (bus) into the conducting equipment.
Same definition as PowerElectronicsUnit.maxPThis is the maximum active power that can be produced by the source. Load sign convention is used, i.e. positive sign means flow out from a TopologicalNode (bus) into the conducting equipment.
Same definition as PowerElectronicsUnit.maxPUsed in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.
The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.
High voltage source reactive injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for steady state solutions.
The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.
The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.
Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.
High voltage source active injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for steady state solutions.
Phase-to-phase nominal voltage.
Same definition as PowerElectronicsConnection.ratedUPositive sequence Thevenin resistance.
Same definition as PowerElectronicsConnection.rZero sequence Thevenin resistance.
Same definition as PowerElectronicsConnection.rNegative sequence Thevenin resistance.
Same definition as PowerElectronicsConnection.rPhase angle of a-phase open circuit used when voltage characteristics need to be imposed at the node associated with the terminal of the energy source, such as when voltages and angles from the transmission level are used as input to the distribution network. The attribute shall be a positive value or zero.
nan
Phase-to-phase open circuit voltage magnitude used when voltage characteristics need to be imposed at the node associated with the terminal of the energy source, such as when voltages and angles from the transmission level are used as input to the distribution network. The attribute shall be a positive value or zero.
Same definition as PowerElectronicsConnection.ratedUPositive sequence Thevenin reactance.
Same definition as PowerElectronicsConnection.xZero sequence Thevenin reactance.
Same definition as PowerElectronicsConnection.xNegative sequence Thevenin reactance.
Same definition as PowerElectronicsConnection.xThe aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.
Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.
The name is any free human readable and possibly non unique text naming the object.