ACDCConverter

Type: object

A unit with valves for three phases, together with unit control equipment, essential protective and switching devices, DC storage capacitors, phase reactors and auxiliaries, if any, used for conversion.

No Additional Properties

VsConverterContainer

Type: object

Hash table of VsConverter objects

No Additional Properties

All properties whose name matches the following regular expression must respect the following conditions

Property name regular expression: ^.+$

VsConverter

Type: object

DC side of the voltage source converter (VSC).

No Additional Properties

LocationPointer

Type: string

Pointer to Location object

SwitchingActionPointer

Type: string

Pointer to SwitchingAction object

TerminalArray

Type: array

Array of Terminal objects

No Additional Items

Each item of this array must be:

Terminal

Type: object

An AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.

No Additional Properties

connected

Type: boolean

The connected status is related to a bus-branch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not.
In a bus-branch model, the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment, where the reactive line charging can be significant, this is a relevant case.

phases

Type: enum (of string)

Represents the normal network phasing condition. If the attribute is missing, three phases (ABC) shall be assumed, except for terminals of grounding classes (specializations of EarthFaultCompensator, GroundDisconnector, and Ground) which will be assumed to be N. Therefore, phase code ABCN is explicitly declared when needed, e.g. for star point grounding equipment.
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.

Must be one of:

  • "ACN"
  • "s2N"
  • "N"
  • "X"
  • "BN"
  • "s12N"
  • "none"
  • "s1"
  • "AC"
  • "ABC"
  • "AB"
  • "s1N"
  • "BC"
  • "XY"
  • "ABCN"
  • "C"
  • "s12"
  • "AN"
  • "XYN"
  • "ABN"
  • "XN"
  • "s2"
  • "CN"
  • "B"
  • "A"
  • "BCN"

sequenceNumber

Type: integer

The orientation of the terminal connections for a multiple terminal conducting equipment. The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the "starting point" for a two terminal branch.

cimObjectType

Type: string

Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.

description

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

aliasName

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

mRID

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

Type: string

The name is any free human readable and possibly non unique text naming the object.

BaseVoltagePointer

Type: string

Pointer to BaseVoltage object

SvStatusArray

Type: array

Array of SvStatus objects

No Additional Items

Each item of this array must be:

SvStatus

Type: object

State variable for status.

No Additional Properties

inService

Type: boolean

The in service status as a result of topology processing. It indicates if the equipment is considered as energized by the power flow. It reflects if the equipment is connected within a solvable island. It does not necessarily reflect whether or not the island was solved by the power flow.

phase

Type: enum (of string)

The individual phase status. If the attribute is unspecified, then three phase model is assumed.

Must be one of:

  • "B"
  • "N"
  • "C"
  • "s2"
  • "A"
  • "s1"

maxValveCurrent

Type: object or number

The maximum current through a valve. It is converter’s configuration data.

UnitSymbol

Type: enum (of string) Default: "A"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

p

Type: object or number

Active power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution in the case a simplified power flow model is used.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

q

Type: object or number

Reactive power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution in the case a simplified power flow model is used.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "VAr"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

cimObjectType

Type: string

Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.

description

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

minUdc

Type: object or number

The minimum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

aggregate

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

networkAnalysisEnabled

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

ratedUdc

Type: object or number

Rated converter DC voltage, also called UdN. The attribute shall be a positive value. It is converter’s configuration data used in power flow. For instance a bipolar HVDC link with value 200 kV has a 400kV difference between the dc lines.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

normallyInService

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

pPccControl

Type: enum (of string)

Kind of control of real power and/or DC voltage.

Must be one of:

  • "pPccAndUdcDroopPilot"
  • "pPcc"
  • "pPccAndUdcDroop"
  • "pPccAndUdcDroopWithCompensation"
  • "udc"
  • "phasePcc"

baseS

Type: object or number

Base apparent power of the converter pole. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "VA"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

switchingLoss

Type: object or number

Switching losses, relative to the base apparent power 'baseS'. Refer to poleLossP. The attribute shall be a positive value.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "WPerA"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

inService

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

qShare

Type: object or number

Reactive power sharing factor among parallel converters on Uac control. The attribute shall be a positive value or zero.

Type: number Default: null

Normally 0 to 100 on a defined base.

UnitSymbol

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

targetPpcc

Type: object or number

Real power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

targetQpcc

Type: object or number

Reactive power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "VAr"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

targetUdc

Type: object or number

Target value for DC voltage magnitude. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

targetUpcc

Type: object or number

Voltage target in AC grid, at point of common coupling. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

droopCompensation

Type: object or number

Compensation constant. Used to compensate for voltage drop when controlling voltage at a distant bus. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "ohm"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

droop

Type: object or number

Droop constant. The pu value is obtained as D [kV/MW] x Sb / Ubdc. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

qPccControl

Type: enum (of string)

Kind of reactive power control.

Must be one of:

  • "voltagePcc"
  • "reactivePcc"
  • "powerFactorPcc"
  • "pulseWidthModulation"

maxModulationIndex

Type: number

The maximum quotient between the AC converter voltage (Uc) and DC voltage (Ud). A factor typically less than 1. It is converter’s configuration data used in power flow.

numberOfValves

Type: integer

Number of valves in the converter. Used in loss calculations.

delta

Type: object or number

Angle between VsConverter.uv and ACDCConverter.uc. It is converter’s state variable used in power flow. The attribute shall be a positive value or zero.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

idc

Type: object or number

Converter DC current, also called Id. It is converter’s state variable, result from power flow.

UnitSymbol

Type: enum (of string) Default: "A"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

valveU0

Type: object or number

Valve threshold voltage, also called Uvalve. Forward voltage drop when the valve is conducting. Used in loss calculations, i.e. the switchLoss depend on numberOfValves * valveU0.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

idleLoss

Type: object or number

Active power loss in pole at no power transfer. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

maxUdc

Type: object or number

The maximum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

targetPowerFactorPcc

Type: number

Power factor target at the AC side, at point of common coupling. The attribute shall be a positive value.

targetPhasePcc

Type: object or number

Phase target at AC side, at point of common coupling. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

targetPWMfactor

Type: number

Magnitude of pulse-modulation factor. The attribute shall be a positive value.

maxP

Type: object or number

Maximum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

minP

Type: object or number

Minimum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

resistiveLoss

Type: object or number

It is converter’s configuration data used in power flow. Refer to poleLossP. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "ohm"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

poleLossP

Type: object or number

The active power loss at a DC Pole
= idleLoss + switchingLoss|Idc| + resitiveLossIdc^2.
For lossless operation Pdc=Pac.
For rectifier operation with losses Pdc=Pac-lossP.
For inverter operation with losses Pdc=Pac+lossP.
It is converter’s state variable used in power flow. The attribute shall be a positive value.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

uc

Type: object or number

Line-to-line converter voltage, the voltage at the AC side of the valve. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

udc

Type: object or number

Converter voltage at the DC side, also called Ud. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

uv

Type: object or number

Line-to-line voltage on the valve side of the converter transformer. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

aliasName

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

mRID

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

name

Type: string

The name is any free human readable and possibly non unique text naming the object.

CsConverterContainer

Type: object

Hash table of CsConverter objects

No Additional Properties

All properties whose name matches the following regular expression must respect the following conditions

Property name regular expression: ^.+$

CsConverter

Type: object

DC side of the current source converter (CSC).
The firing angle controls the dc voltage at the converter, both for rectifier and inverter. The difference between the dc voltages of the rectifier and inverter determines the dc current. The extinction angle is used to limit the dc voltage at the inverter, if needed, and is not used in active power control. The firing angle, transformer tap position and number of connected filters are the primary means to control a current source dc line. Higher level controls are built on top, e.g. dc voltage, dc current and active power. From a steady state perspective it is sufficient to specify the wanted active power transfer (ACDCConverter.targetPpcc) and the control functions will set the dc voltage, dc current, firing angle, transformer tap position and number of connected filters to meet this. Therefore attributes targetAlpha and targetGamma are not applicable in this case.
The reactive power consumed by the converter is a function of the firing angle, transformer tap position and number of connected filter, which can be approximated with half of the active power. The losses is a function of the dc voltage and dc current.
The attributes minAlpha and maxAlpha define the range of firing angles for rectifier operation between which no discrete tap changer action takes place. The range is typically 10-18 degrees.
The attributes minGamma and maxGamma define the range of extinction angles for inverter operation between which no discrete tap changer action takes place. The range is typically 17-20 degrees.

No Additional Properties

LocationPointer

Type: string

Pointer to Location object

SwitchingActionPointer

Type: string

Pointer to SwitchingAction object

BaseVoltagePointer

Type: string

Pointer to BaseVoltage object

alpha

Type: object or number

Firing angle that determines the dc voltage at the converter dc terminal. Typical value between 10 degrees and 18 degrees for a rectifier. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

gamma

Type: object or number

Extinction angle. It is used to limit the dc voltage at the inverter if needed. Typical value between 17 degrees and 20 degrees for an inverter. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

maxAlpha

Type: object or number

Maximum firing angle. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

maxGamma

Type: object or number

Maximum extinction angle. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

minAlpha

Type: object or number

Minimum firing angle. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

minGamma

Type: object or number

Minimum extinction angle. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

targetAlpha

Type: object or number

Target firing angle. It is converter’s control variable used in power flow. It is only applicable for rectifier if continuous tap changer control is used. Allowed values are within the range minAlpha<=targetAlpha<=maxAlpha. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

targetGamma

Type: object or number

Target extinction angle. It is converter’s control variable used in power flow. It is only applicable for inverter if continuous tap changer control is used. Allowed values are within the range minGamma<=targetGamma<=maxGamma. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "deg"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

targetIdc

Type: object or number

DC current target value. It is converter’s control variable used in power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "A"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

minIdc

Type: object or number

The minimum direct current (Id) on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "A"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

operatingMode

Type: enum (of string)

Indicates whether the DC pole is operating as an inverter or as a rectifier. It is converter’s control variable used in power flow.

Must be one of:

  • "inverter"
  • "rectifier"

q

Type: object or number

Reactive power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution in the case a simplified power flow model is used.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "VAr"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

p

Type: object or number

Active power at the point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution in the case a simplified power flow model is used.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

cimObjectType

Type: string

Used in RAVENS Schema to identify the corresponding CIM Object Type of the JSON object.

description

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

minP

Type: object or number

Minimum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

aggregate

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

networkAnalysisEnabled

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

ratedUdc

Type: object or number

Rated converter DC voltage, also called UdN. The attribute shall be a positive value. It is converter’s configuration data used in power flow. For instance a bipolar HVDC link with value 200 kV has a 400kV difference between the dc lines.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

normallyInService

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

mRID

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

baseS

Type: object or number

Base apparent power of the converter pole. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "VA"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

switchingLoss

Type: object or number

Switching losses, relative to the base apparent power 'baseS'. Refer to poleLossP. The attribute shall be a positive value.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "WPerA"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

inService

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

targetPpcc

Type: object or number

Real power injection target in AC grid, at point of common coupling. Load sign convention is used, i.e. positive sign means flow out from a node.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

targetUdc

Type: object or number

Target value for DC voltage magnitude. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

valveU0

Type: object or number

Valve threshold voltage, also called Uvalve. Forward voltage drop when the valve is conducting. Used in loss calculations, i.e. the switchLoss depend on numberOfValves * valveU0.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

numberOfValves

Type: integer

Number of valves in the converter. Used in loss calculations.

idc

Type: object or number

Converter DC current, also called Id. It is converter’s state variable, result from power flow.

UnitSymbol

Type: enum (of string) Default: "A"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

idleLoss

Type: object or number

Active power loss in pole at no power transfer. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

maxIdc

Type: object or number

The maximum direct current (Id) on the DC side at which the converter should operate. It is converter’s configuration data use in power flow. The attribute shall be a positive value.

UnitSymbol

Type: enum (of string) Default: "A"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

maxUdc

Type: object or number

The maximum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

minUdc

Type: object or number

The minimum voltage on the DC side at which the converter should operate. It is converter’s configuration data used in power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

poleLossP

Type: object or number

The active power loss at a DC Pole
= idleLoss + switchingLoss|Idc| + resitiveLossIdc^2.
For lossless operation Pdc=Pac.
For rectifier operation with losses Pdc=Pac-lossP.
For inverter operation with losses Pdc=Pac+lossP.
It is converter’s state variable used in power flow. The attribute shall be a positive value.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

ratedIdc

Type: object or number

Rated converter DC current, also called IdN. The attribute shall be a positive value. It is converter’s configuration data used in power flow.

UnitSymbol

Type: enum (of string) Default: "A"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

maxP

Type: object or number

Maximum active power limit. The value is overwritten by values of VsCapabilityCurve, if present.

Type: number Default: null

nan

UnitSymbol

Type: enum (of string) Default: "W"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

resistiveLoss

Type: object or number

It is converter’s configuration data used in power flow. Refer to poleLossP. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "ohm"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

uc

Type: object or number

Line-to-line converter voltage, the voltage at the AC side of the valve. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

udc

Type: object or number

Converter voltage at the DC side, also called Ud. It is converter’s state variable, result from power flow. The attribute shall be a positive value.

UnitMultiplier

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "f"
  • "c"
  • "G"
  • "d"
  • "z"
  • "p"
  • "y"
  • "h"
  • "Y"
  • "a"
  • "none"
  • "k"
  • "m"
  • "n"
  • "E"
  • "da"
  • "T"
  • "M"
  • "P"
  • "Z"
  • "micro"

UnitSymbol

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "JPerkg"
  • "NPerm"
  • "WPerW"
  • "JPermol"
  • "WPerm2sr"
  • "V"
  • "A2h"
  • "JPerK"
  • "m3Perkg"
  • "HzPerHz"
  • "T"
  • "Vh"
  • "tonne"
  • "JPerm2"
  • "CPerkg"
  • "VPerHz"
  • "ohm"
  • "K"
  • "m3Compensated"
  • "lx"
  • "lPerh"
  • "APerm"
  • "charPers"
  • "katPerm3"
  • "Pas"
  • "ohmPerm"
  • "radPers2"
  • "Btu"
  • "WPers"
  • "h"
  • "lPerl"
  • "l"
  • "As"
  • "cosPhi"
  • "W"
  • "count"
  • "PaPers"
  • "onePerHz"
  • "m3Pers"
  • "KPers"
  • "Vs"
  • "m2Pers"
  • "Ah"
  • "deg"
  • "mPers2"
  • "lm"
  • "d"
  • "JPerkgK"
  • "m"
  • "min"
  • "dB"
  • "Gy"
  • "Nm"
  • "JPerm3"
  • "sPers"
  • "Q"
  • "rev"
  • "N"
  • "Bq"
  • "WPermK"
  • "GyPers"
  • "HPerm"
  • "molPerkg"
  • "molPerm3"
  • "Wb"
  • "VPerm"
  • "WPerm2"
  • "kn"
  • "CPerm2"
  • "anglemin"
  • "Oe"
  • "kgm"
  • "character"
  • "APerA"
  • "A2s"
  • "Qh"
  • "JPers"
  • "Hz"
  • "rad"
  • "kat"
  • "degC"
  • "bar"
  • "M"
  • "molPermol"
  • "kgPerJ"
  • "J"
  • "HzPers"
  • "WPersr"
  • "anglesec"
  • "F"
  • "Mx"
  • "ha"
  • "SPerm"
  • "gal"
  • "mmHg"
  • "m2"
  • "mPers"
  • "V2h"
  • "m3"
  • "G"
  • "H"
  • "mol"
  • "rotPers"
  • "VAh"
  • "mPerm3"
  • "onePerm"
  • "V2"
  • "WPerA"
  • "Pa"
  • "kgPerm3"
  • "CPerm3"
  • "Sv"
  • "S"
  • "JPermolK"
  • "ft3"
  • "Wh"
  • "radPers"
  • "ohmm"
  • "kgm2"
  • "m3Perh"
  • "dBm"
  • "VA"
  • "A2"
  • "s"
  • "therm"
  • "VArh"
  • "cd"
  • "VPerV"
  • "gPerg"
  • "kg"
  • "A"
  • "m3Uncompensated"
  • "ppm"
  • "FPerm"
  • "C"
  • "sr"
  • "none"
  • "VPerVAr"
  • "VAr"
  • "VPerVA"
  • "lPers"

Type: number Default: null

nan

aliasName

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

pPccControl

Type: enum (of string)

Kind of active power control.

Must be one of:

  • "dcCurrent"
  • "dcVoltage"
  • "activePower"

name

Type: string

The name is any free human readable and possibly non unique text naming the object.