TransformerEndInfo

Type: object

Transformer end data.

Type: array

No-load test results determine core admittance parameters. They include exciting current and core loss measurements from applying voltage to one winding. The excitation may be positive sequence or zero sequence. The test may be repeated at different voltages to measure saturation.

No Additional Items

Each item of this array must be:

Type: object

No-load test results determine core admittance parameters. They include exciting current and core loss measurements from applying voltage to one winding. The excitation may be positive sequence or zero sequence. The test may be repeated at different voltages to measure saturation.

Type: object or number

Temperature at which the test is conducted.

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "p"
  • "n"
  • "micro"
  • "m"
  • "c"
  • "d"
  • "k"
  • "M"
  • "G"
  • "T"
  • "none"
  • "y"
  • "z"
  • "a"
  • "f"
  • "da"
  • "h"
  • "P"
  • "E"
  • "Z"
  • "Y"

Type: enum (of string) Default: "degC"

nan

Must be one of:

  • "none"
  • "m"
  • "kg"
  • "s"
  • "A"
  • "K"
  • "mol"
  • "cd"
  • "deg"
  • "rad"
  • "sr"
  • "Gy"
  • "Bq"
  • "degC"
  • "Sv"
  • "F"
  • "C"
  • "S"
  • "H"
  • "V"
  • "ohm"
  • "J"
  • "N"
  • "Hz"
  • "lx"
  • "lm"
  • "Wb"
  • "T"
  • "W"
  • "Pa"
  • "m2"
  • "m3"
  • "mPers"
  • "mPers2"
  • "m3Pers"
  • "mPerm3"
  • "kgm"
  • "kgPerm3"
  • "WPermK"
  • "JPerK"
  • "ppm"
  • "rotPers"
  • "radPers"
  • "VA"
  • "VAr"
  • "cosPhi"
  • "Vs"
  • "V2"
  • "As"
  • "A2"
  • "A2s"
  • "VAh"
  • "Wh"
  • "VArh"
  • "VPerHz"
  • "HzPers"
  • "character"
  • "charPers"
  • "kgm2"
  • "dB"
  • "WPers"
  • "lPers"
  • "dBm"
  • "h"
  • "min"
  • "Q"
  • "Qh"
  • "ohmm"
  • "APerm"
  • "V2h"
  • "A2h"
  • "Ah"
  • "count"
  • "ft3"
  • "m3Perh"
  • "gal"
  • "Btu"
  • "l"
  • "lPerh"
  • "lPerl"
  • "gPerg"
  • "molPerm3"
  • "molPermol"
  • "molPerkg"
  • "sPers"
  • "HzPerHz"
  • "VPerV"
  • "APerA"
  • "VPerVA"
  • "rev"
  • "kat"
  • "JPerkg"
  • "m3Uncompensated"
  • "m3Compensated"
  • "WPerW"
  • "therm"
  • "onePerm"
  • "m3Perkg"
  • "Pas"
  • "Nm"
  • "NPerm"
  • "radPers2"
  • "WPerm2"
  • "JPerkgK"
  • "JPerm3"
  • "VPerm"
  • "CPerm3"
  • "CPerm2"
  • "FPerm"
  • "HPerm"
  • "JPermol"
  • "JPermolK"
  • "CPerkg"
  • "GyPers"
  • "WPersr"
  • "WPerm2sr"
  • "katPerm3"
  • "d"
  • "anglemin"
  • "anglesec"
  • "ha"
  • "tonne"
  • "bar"
  • "mmHg"
  • "M"
  • "kn"
  • "Vh"
  • "Mx"
  • "G"
  • "Oe"
  • "WPerA"
  • "SPerm"
  • "onePerHz"
  • "VPerVAr"
  • "ohmPerm"
  • "kgPerJ"
  • "JPers"
  • "m2Pers"
  • "JPerm2"
  • "KPers"
  • "PaPers"

Type: object or number

Exciting current measured from a positive-sequence or single-phase excitation test.

Type: number Default: null

Normally 0 to 100 on a defined base.

Type: object or number

Exciting current measured from a zero-sequence open-circuit excitation test.

Same definition as NoLoadTest.excitingCurrent

Type: object or number

Base power at which the tests are conducted, usually equal to the rateds of one of the involved transformer ends.

Type: object or number

Losses measured from a positive-sequence or single-phase excitation test.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: object or number

Losses measured from a zero-sequence excitation test.

Same definition as NoLoadTest.loss

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: array

Short-circuit test results determine mesh impedance parameters. They include load losses and leakage impedances. For three-phase windings, the excitation can be a positive sequence (the default) or a zero sequence. There shall be at least one grounded winding.

No Additional Items

Each item of this array must be:

Type: object

Short-circuit test results determine mesh impedance parameters. They include load losses and leakage impedances. For three-phase windings, the excitation can be a positive sequence (the default) or a zero sequence. There shall be at least one grounded winding.

Type: object or number

Load losses from a positive-sequence or single-phase short-circuit test.

Same definition as NoLoadTest.loss

Type: integer

Tap step number for the energised end of the test pair.

Type: object or number

Base power at which the tests are conducted, usually equal to the rateds of one of the involved transformer ends.

Same definition as TransformerTest.basePower

Type: integer

Tap step number for the grounded end of the test pair.

Type: object or number

Load losses from a zero-sequence short-circuit test.

Same definition as NoLoadTest.loss

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: object or number

Apparent power that the winding can carry under emergency conditions (also called long-term emergency power).

Same definition as TransformerTest.basePower

Type: integer

Winding phase angle where 360 degrees are represented with clock hours, so the valid values are {0, ..., 11}. For example, to express the second winding in code 'Dyn11', set attributes as follows: 'endNumber'=2, 'connectionKind' = Yn and 'phaseAngleClock' = 11.

Type: object or number

Rated voltage: phase-phase for three-phase windings, and either phase-phase or phase-neutral for single-phase windings.

Same definition as NoLoadTest.energisedEndVoltage

Type: object or number

Basic insulation level voltage rating.

Same definition as NoLoadTest.energisedEndVoltage

Type: enum (of string)

Kind of connection.

Must be one of:

  • "D"
  • "Y"
  • "Z"
  • "Yn"
  • "Zn"
  • "A"
  • "I"

Type: object or number

DC resistance.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "ohm"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Normal apparent power rating.

Same definition as TransformerTest.basePower

Type: object or number

Apparent power that this winding can carry for a short period of time (in emergency).

Same definition as TransformerTest.basePower

Type: integer

Number for this transformer end, corresponding to the end's order in the PowerTransformer.vectorGroup attribute. Highest voltage winding should be 1.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.