PowerElectronicsConnection

Type: object

A connection to the AC network for energy production or consumption that uses power electronics rather than rotating machines.

Type: string

Type: array

An AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.

No Additional Items

Each item of this array must be:

Type: object

An AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.

Type: boolean

The connected status is related to a bus-branch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not.
In a bus-branch model, the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment, where the reactive line charging can be significant, this is a relevant case.

Type: enum (of string)

Represents the normal network phasing condition. If the attribute is missing, three phases (ABC) shall be assumed, except for terminals of grounding classes (specializations of EarthFaultCompensator, GroundDisconnector, and Ground) which will be assumed to be N. Therefore, phase code ABCN is explicitly declared when needed, e.g. for star point grounding equipment.
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.

Must be one of:

  • "ABCN"
  • "ABC"
  • "ABN"
  • "ACN"
  • "BCN"
  • "AB"
  • "AC"
  • "BC"
  • "AN"
  • "BN"
  • "CN"
  • "A"
  • "B"
  • "C"
  • "N"
  • "s1N"
  • "s2N"
  • "s12N"
  • "s1"
  • "s2"
  • "s12"
  • "none"
  • "X"
  • "XY"
  • "XN"
  • "XYN"

Type: integer

The orientation of the terminal connections for a multiple terminal conducting equipment. The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the "starting point" for a two terminal branch.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: object

A generating unit or battery or aggregation that connects to the AC network using power electronics rather than rotating machines.

Type: object

An electrochemical energy storage device.

Type: object

nan

Type: enum (of string)

nan

Must be one of:

  • "constantPFixedV"
  • "constantAdmittance"
  • "constantPConstantQCurrentLimited"
  • "constantPF"
  • "constantPFixedQ"
  • "constantPFixedQConstantReactance"

Type: object or number

Full energy storage capacity of the battery. The attribute shall be a positive value.

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "p"
  • "n"
  • "micro"
  • "m"
  • "c"
  • "d"
  • "k"
  • "M"
  • "G"
  • "T"
  • "none"
  • "y"
  • "z"
  • "a"
  • "f"
  • "da"
  • "h"
  • "P"
  • "E"
  • "Z"
  • "Y"

Type: enum (of string) Default: "Wh"

nan

Must be one of:

  • "none"
  • "m"
  • "kg"
  • "s"
  • "A"
  • "K"
  • "mol"
  • "cd"
  • "deg"
  • "rad"
  • "sr"
  • "Gy"
  • "Bq"
  • "degC"
  • "Sv"
  • "F"
  • "C"
  • "S"
  • "H"
  • "V"
  • "ohm"
  • "J"
  • "N"
  • "Hz"
  • "lx"
  • "lm"
  • "Wb"
  • "T"
  • "W"
  • "Pa"
  • "m2"
  • "m3"
  • "mPers"
  • "mPers2"
  • "m3Pers"
  • "mPerm3"
  • "kgm"
  • "kgPerm3"
  • "WPermK"
  • "JPerK"
  • "ppm"
  • "rotPers"
  • "radPers"
  • "VA"
  • "VAr"
  • "cosPhi"
  • "Vs"
  • "V2"
  • "As"
  • "A2"
  • "A2s"
  • "VAh"
  • "Wh"
  • "VArh"
  • "VPerHz"
  • "HzPers"
  • "character"
  • "charPers"
  • "kgm2"
  • "dB"
  • "WPers"
  • "lPers"
  • "dBm"
  • "h"
  • "min"
  • "Q"
  • "Qh"
  • "ohmm"
  • "APerm"
  • "V2h"
  • "A2h"
  • "Ah"
  • "count"
  • "ft3"
  • "m3Perh"
  • "gal"
  • "Btu"
  • "l"
  • "lPerh"
  • "lPerl"
  • "gPerg"
  • "molPerm3"
  • "molPermol"
  • "molPerkg"
  • "sPers"
  • "HzPerHz"
  • "VPerV"
  • "APerA"
  • "VPerVA"
  • "rev"
  • "kat"
  • "JPerkg"
  • "m3Uncompensated"
  • "m3Compensated"
  • "WPerW"
  • "therm"
  • "onePerm"
  • "m3Perkg"
  • "Pas"
  • "Nm"
  • "NPerm"
  • "radPers2"
  • "WPerm2"
  • "JPerkgK"
  • "JPerm3"
  • "VPerm"
  • "CPerm3"
  • "CPerm2"
  • "FPerm"
  • "HPerm"
  • "JPermol"
  • "JPermolK"
  • "CPerkg"
  • "GyPers"
  • "WPersr"
  • "WPerm2sr"
  • "katPerm3"
  • "d"
  • "anglemin"
  • "anglesec"
  • "ha"
  • "tonne"
  • "bar"
  • "mmHg"
  • "M"
  • "kn"
  • "Vh"
  • "Mx"
  • "G"
  • "Oe"
  • "WPerA"
  • "SPerm"
  • "onePerHz"
  • "VPerVAr"
  • "ohmPerm"
  • "kgPerJ"
  • "JPers"
  • "m2Pers"
  • "JPerm2"
  • "KPers"
  • "PaPers"

Type: object or number

Amount of energy currently stored. The attribute shall be a positive value or zero and lower than BatteryUnit.ratedE.

Same definition as BatteryUnit.ratedE

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: enum (of string)

The current state of the battery (charging, full, etc.).

Must be one of:

  • "discharging"
  • "waiting"
  • "full"
  • "empty"
  • "charging"

Type: object or number

Minimum active power limit. This is the minimum (nameplate) limit for the unit.

Same definition as PowerElectronicsUnit.maxP

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: object

A photovoltaic device or an aggregation of such devices.

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: object or number

Maximum active power limit. This is the maximum (nameplate) limit for the unit.

Same definition as PowerElectronicsUnit.maxP

Type: object or number

Minimum active power limit. This is the minimum (nameplate) limit for the unit.

Same definition as PowerElectronicsUnit.maxP

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: object

A wind generating unit that connects to the AC network with power electronics rather than rotating machines or an aggregation of such units.

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: object or number

Maximum active power limit. This is the maximum (nameplate) limit for the unit.

Same definition as PowerElectronicsUnit.maxP

Type: object or number

Minimum active power limit. This is the minimum (nameplate) limit for the unit.

Same definition as PowerElectronicsUnit.maxP

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: string

Defines a system base voltage which is referenced.

Type: array

A single phase of a power electronics connection.

No Additional Items

Each item of this array must be:

Type: object

A single phase of a power electronics connection.

Type: enum (of string)

Phase of this energy producer component. If the energy producer is wye connected, the connection is from the indicated phase to the central ground or neutral point. If the energy producer is delta connected, the phase indicates an energy producer connected from the indicated phase to the next logical non-neutral phase.

Must be one of:

  • "A"
  • "B"
  • "C"
  • "N"
  • "s1"
  • "s2"

Type: object or number

Active power injection. Load sign convention is used, i.e. positive sign means flow into the equipment from the network.

Same definition as PowerElectronicsUnit.maxP

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: array

State variable for status.

No Additional Items

Each item of this array must be:

Type: object

State variable for status.

Type: boolean

The in service status as a result of topology processing. It indicates if the equipment is considered as energized by the power flow. It reflects if the equipment is connected within a solvable island. It does not necessarily reflect whether or not the island was solved by the power flow.

Type: enum (of string)

The individual phase status. If the attribute is unspecified, then three phase model is assumed.

Same definition as PowerElectronicsConnectionPhase.phase

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: boolean

Specifies the regulation status of the equipment. True is regulating, false is not regulating.

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: object or number

Maximum fault current this device will contribute, in per-unit of rated current, before the converter protection will trip or bypass.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "none"

nan

Same definition as unit

Type: number Default: null

nan

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: object or number

Maximum reactive power limit. This is the maximum (nameplate) limit for the unit.

Same definition as PowerElectronicsConnectionPhase.q

Type: object or number

Minimum reactive power limit for the unit. This is the minimum (nameplate) limit for the unit.

Same definition as PowerElectronicsConnectionPhase.q

Type: object or number

Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.

Same definition as PowerElectronicsUnit.maxP

Type: object or number

Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.

Same definition as PowerElectronicsConnectionPhase.q

Type: object or number

Equivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "ohm"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Zero sequence resistance of the synchronous machine.

Same definition as PowerElectronicsConnection.r

Type: object or number

Nameplate apparent power rating for the unit.
The attribute shall have a positive value.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "VA"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Rated voltage (nameplate data, Ur in IEC 60909-0). It is primarily used for short circuit data exchange according to IEC 60909.
The attribute shall be a positive value.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "V"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Negative sequence Thevenin resistance.

Same definition as PowerElectronicsConnection.r

Type: object or number

Positive sequence Thevenin reactance.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "ohm"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Zero sequence Thevenin reactance.

Same definition as PowerElectronicsConnection.x

Type: object or number

Negative sequence Thevenin reactance.

Same definition as PowerElectronicsConnection.x

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.