SolarGeneratingUnit

Type: object

A solar thermal generating unit, connected to the grid by means of a rotating machine. This class does not represent photovoltaic (PV) generation.

Type: object

The generating unit's Operator-approved current operating schedule (or plan), typically produced with the aid of unit commitment type analyses. The X-axis represents absolute time. The Y1-axis represents the status (0=off-line and unavailable: 1=available: 2=must run: 3=must run at fixed power value: etc.). The Y2-axis represents the must run fixed power value where required.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: enum (of string)

Multiplier for value2.

Must be one of:

  • "p"
  • "n"
  • "micro"
  • "m"
  • "c"
  • "d"
  • "k"
  • "M"
  • "G"
  • "T"
  • "none"
  • "y"
  • "z"
  • "a"
  • "f"
  • "da"
  • "h"
  • "P"
  • "E"
  • "Z"
  • "Y"

Type: object or number

The time between each pair of subsequent regular time points in sequence order.

Type: enum (of string) Default: "s"

nan

Must be one of:

  • "none"
  • "m"
  • "kg"
  • "s"
  • "A"
  • "K"
  • "mol"
  • "cd"
  • "deg"
  • "rad"
  • "sr"
  • "Gy"
  • "Bq"
  • "degC"
  • "Sv"
  • "F"
  • "C"
  • "S"
  • "H"
  • "V"
  • "ohm"
  • "J"
  • "N"
  • "Hz"
  • "lx"
  • "lm"
  • "Wb"
  • "T"
  • "W"
  • "Pa"
  • "m2"
  • "m3"
  • "mPers"
  • "mPers2"
  • "m3Pers"
  • "mPerm3"
  • "kgm"
  • "kgPerm3"
  • "WPermK"
  • "JPerK"
  • "ppm"
  • "rotPers"
  • "radPers"
  • "VA"
  • "VAr"
  • "cosPhi"
  • "Vs"
  • "V2"
  • "As"
  • "A2"
  • "A2s"
  • "VAh"
  • "Wh"
  • "VArh"
  • "VPerHz"
  • "HzPers"
  • "character"
  • "charPers"
  • "kgm2"
  • "dB"
  • "WPers"
  • "lPers"
  • "dBm"
  • "h"
  • "min"
  • "Q"
  • "Qh"
  • "ohmm"
  • "APerm"
  • "V2h"
  • "A2h"
  • "Ah"
  • "count"
  • "ft3"
  • "m3Perh"
  • "gal"
  • "Btu"
  • "l"
  • "lPerh"
  • "lPerl"
  • "gPerg"
  • "molPerm3"
  • "molPermol"
  • "molPerkg"
  • "sPers"
  • "HzPerHz"
  • "VPerV"
  • "APerA"
  • "VPerVA"
  • "rev"
  • "kat"
  • "JPerkg"
  • "m3Uncompensated"
  • "m3Compensated"
  • "WPerW"
  • "therm"
  • "onePerm"
  • "m3Perkg"
  • "Pas"
  • "Nm"
  • "NPerm"
  • "radPers2"
  • "WPerm2"
  • "JPerkgK"
  • "JPerm3"
  • "VPerm"
  • "CPerm3"
  • "CPerm2"
  • "FPerm"
  • "HPerm"
  • "JPermol"
  • "JPermolK"
  • "CPerkg"
  • "GyPers"
  • "WPersr"
  • "WPerm2sr"
  • "katPerm3"
  • "d"
  • "anglemin"
  • "anglesec"
  • "ha"
  • "tonne"
  • "bar"
  • "mmHg"
  • "M"
  • "kn"
  • "Vh"
  • "Mx"
  • "G"
  • "Oe"
  • "WPerA"
  • "SPerm"
  • "onePerHz"
  • "VPerVAr"
  • "ohmPerm"
  • "kgPerJ"
  • "JPers"
  • "m2Pers"
  • "JPerm2"
  • "KPers"
  • "PaPers"

Type: number Default: null

Time, in seconds

Type: string

The time for the first time point. The value can be a time of day, not a specific date.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The time for the last time point. The value can be a time of day, not a specific date.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: array

Relationship between unit operating cost (Y-axis) and unit output active power (X-axis). The operating cost curve for thermal units is derived from heat input and fuel costs. The operating cost curve for hydro units is derived from water flow rates and equivalent water costs.

No Additional Items

Each item of this array must be:

Type: object

Relationship between unit operating cost (Y-axis) and unit output active power (X-axis). The operating cost curve for thermal units is derived from heat input and fuel costs. The operating cost curve for hydro units is derived from water flow rates and equivalent water costs.

Type: boolean

Flag is set to true when output is expressed in net active power.

Type: enum (of string)

The style or shape of the curve.

Must be one of:

  • "constantYValue"
  • "straightLineYValues"

Type: enum (of string)

The X-axis units of measure.

Same definition as unit

Type: enum (of string)

The Y1-axis units of measure.

Same definition as unit

Type: enum (of string)

The Y2-axis units of measure.

Same definition as unit

Type: enum (of string)

The Y3-axis units of measure.

Same definition as unit

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: object or number

Governor motor position limit.

Type: enum (of string) Default: "none"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Governor Speed Changer Droop. This is the change in generator power output divided by the change in frequency normalized by the nominal power of the generator and the nominal frequency and expressed in percent and negated. A positive value of speed change droop provides additional generator output upon a drop in frequency.

Type: enum (of string) Default: "none"

nan

Same definition as unit

Type: number Default: null

Normally 0 to 100 on a defined base.

Type: object or number

High limit for secondary (AGC) control.

Type: enum (of string) Default: "W"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Default initial active power which is used to store a powerflow result for the initial active power for this unit in this network configuration.

Same definition as GeneratingUnit.highControlLimit

Type: number

Generating unit long term economic participation factor.

Type: object or number

Low limit for secondary (AGC) control.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

The normal maximum rate the generating unit active power output can be lowered by control actions.

Type: enum (of string) Default: "WPers"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Maximum high economic active power limit, that should not exceed the maximum operating active power limit.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

Maximum allowable spinning reserve. Spinning reserve will never be considered greater than this value regardless of the current operating point.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

This is the maximum operating active power limit the dispatcher can enter for this unit.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

Low economic active power limit that shall be greater than or equal to the minimum operating active power limit.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

Minimum time interval between unit shutdown and startup.

Same definition as RegularIntervalSchedule.timeStep

Type: object or number

This is the minimum operating active power limit the dispatcher can enter for this unit.

Same definition as GeneratingUnit.highControlLimit

Type: object or integer

Detail level of the generator model data.

Type: enum (of string) Default: "none"

nan

Same definition as unit

Type: integer Default: null

nan

Type: object or number

The nominal power of the generating unit. Used to give precise meaning to percentage based attributes such as the governor speed change droop (governorSCD attribute).
The attribute shall be a positive value equal to or less than RotatingMachine.ratedS.

Same definition as GeneratingUnit.highControlLimit

Type: number

Generating unit economic participation factor. The sum of the participation factors across generating units does not have to sum to one. It is used for representing distributed slack participation factor. The attribute shall be a positive value or zero.

Type: number

Defined as: 1 / ( 1 - Incremental Transmission Loss); with the Incremental Transmission Loss expressed as a plus or minus value. The typical range of penalty factors is (0.9 to 1.1).

Type: object or number

The normal maximum rate the generating unit active power output can be raised by control actions.

Same definition as GeneratingUnit.lowerRampRate

Type: object or number

The unit's gross rated maximum capacity (book value).
The attribute shall be a positive value.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

The gross rated minimum generation level which the unit can safely operate at while delivering power to the transmission grid.
The attribute shall be a positive value.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

The net rated maximum capacity determined by subtracting the auxiliary power used to operate the internal plant machinery from the rated gross maximum capacity.
The attribute shall be a positive value.

Same definition as GeneratingUnit.highControlLimit

Type: number

Generating unit short term economic participation factor.

Type: object

The initial startup cost incurred for each start of the GeneratingUnit.

Type: enum (of string) Default: null

nan

Must be one of:

  • "AUD"
  • "CHF"
  • "AFN"
  • "AED"
  • "ALL"
  • "AMD"
  • "ANG"
  • "AOA"
  • "ARS"
  • "AWG"
  • "AZN"
  • "BAM"
  • "BBD"
  • "BDT"
  • "BGN"
  • "BHD"
  • "BIF"
  • "BMD"
  • "BND"
  • "BOB"
  • "BOV"
  • "BRL"
  • "BSD"
  • "BTN"
  • "BWP"
  • "BYR"
  • "BZD"
  • "CAD"
  • "CDF"
  • "CLF"
  • "CLP"
  • "CNY"
  • "ZAR"
  • "COP"
  • "COU"
  • "CRC"
  • "CUC"
  • "CUP"
  • "CVE"
  • "CZK"
  • "DJF"
  • "DKK"
  • "DOP"
  • "DZD"
  • "EEK"
  • "EGP"
  • "ERN"
  • "ETB"
  • "EUR"
  • "FJD"
  • "FKP"
  • "GBP"
  • "GEL"
  • "GHS"
  • "GIP"
  • "GMD"
  • "GNF"
  • "GTQ"
  • "GYD"
  • "HKD"
  • "HNL"
  • "HRK"
  • "HTG"
  • "HUF"
  • "IDR"
  • "ILS"
  • "INR"
  • "IQD"
  • "IRR"
  • "ISK"
  • "JMD"
  • "JOD"
  • "JPY"
  • "KES"
  • "KGS"
  • "KHR"
  • "KMF"
  • "KPW"
  • "KRW"
  • "KWD"
  • "KYD"
  • "KZT"
  • "LAK"
  • "LBP"
  • "LKR"
  • "LRD"
  • "LSL"
  • "LTL"
  • "LVL"
  • "LYD"
  • "MAD"
  • "MDL"
  • "MGA"
  • "MKD"
  • "MMK"
  • "MNT"
  • "MOP"
  • "MRO"
  • "MUR"
  • "MVR"
  • "MWK"
  • "MXN"
  • "MYR"
  • "MZN"
  • "NAD"
  • "NGN"
  • "NIO"
  • "NOK"
  • "NPR"
  • "NZD"
  • "OMR"
  • "PAB"
  • "PEN"
  • "PGK"
  • "PHP"
  • "PKR"
  • "PLN"
  • "PYG"
  • "QAR"
  • "RON"
  • "RSD"
  • "RUB"
  • "RWF"
  • "SAR"
  • "SBD"
  • "SCR"
  • "SDG"
  • "SEK"
  • "SGD"
  • "SHP"
  • "SLL"
  • "SOS"
  • "SRD"
  • "STD"
  • "SYP"
  • "SZL"
  • "THB"
  • "TJS"
  • "TMT"
  • "TND"
  • "TOP"
  • "TRY"
  • "TTD"
  • "TWD"
  • "TZS"
  • "UAH"
  • "UGX"
  • "USD"
  • "UYU"
  • "UZS"
  • "VEF"
  • "VND"
  • "VUV"
  • "WST"
  • "XAF"
  • "XCD"
  • "XOF"
  • "XPF"
  • "YER"
  • "ZMK"
  • "ZWL"

Type: number Default: null

nan

Type: object or number

Time it takes to get the unit on-line, from the time that the prime mover mechanical power is applied.

Same definition as RegularIntervalSchedule.timeStep

Type: number

Generating unit economic participation factor.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: object

The variable cost component of production per unit of ActivePower.

Same definition as GeneratingUnit.startupCost

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

Type: object or number

The efficiency of the unit in converting the fuel into electrical energy.

Same definition as GeneratingUnit.governorSCD

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: object or number

The planned unused capacity (spinning reserve) which can be used to support emergency load.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

The planned unused capacity which can be used to support automatic control overruns.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

For dispatchable units, this value represents the economic active power basepoint, for units that are not dispatchable, this value represents the fixed generation value. The value shall be between the operating low and high limits.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

Unit control error deadband. When a unit's desired active power change is less than this deadband, then no control pulses will be sent to the unit.

Same definition as GeneratingUnit.highControlLimit

Type: object or number

Pulse high limit which is the largest control pulse that the unit can respond to.

Same definition as RegularIntervalSchedule.timeStep

Type: object or number

Pulse low limit which is the smallest control pulse that the unit can respond to.

Same definition as RegularIntervalSchedule.timeStep

Type: object or number

Unit response rate which specifies the active power change for a control pulse of one second in the most responsive loading level of the unit.

Same definition as GeneratingUnit.lowerRampRate

Type: object or number

The efficiency of the unit in converting mechanical energy, from the prime mover, into electrical energy.

Same definition as GeneratingUnit.governorSCD

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: enum (of string)

The unit control mode.

Must be one of:

  • "setpoint"
  • "pulse"

Type: enum (of string)

The source of controls for a generating unit. Defines the control status of the generating unit.

Must be one of:

  • "unavailable"
  • "offAGC"
  • "onAGC"
  • "plantControl"