StaticVarCompensator

Type: object

A facility for providing variable and controllable shunt reactive power. The SVC typically consists of a stepdown transformer, filter, thyristor-controlled reactor, and thyristor-switched capacitor arms.

The SVC may operate in fixed MVar output mode or in voltage control mode. When in voltage control mode, the output of the SVC will be proportional to the deviation of voltage at the controlled bus from the voltage setpoint. The SVC characteristic slope defines the proportion. If the voltage at the controlled bus is equal to the voltage setpoint, the SVC MVar output is zero.

Type: string

Type: array

An AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.

No Additional Items

Each item of this array must be:

Type: object

An AC electrical connection point to a piece of conducting equipment. Terminals are connected at physical connection points called connectivity nodes.

Type: boolean

The connected status is related to a bus-branch model and the topological node to terminal relation. True implies the terminal is connected to the related topological node and false implies it is not.
In a bus-branch model, the connected status is used to tell if equipment is disconnected without having to change the connectivity described by the topological node to terminal relation. A valid case is that conducting equipment can be connected in one end and open in the other. In particular for an AC line segment, where the reactive line charging can be significant, this is a relevant case.

Type: enum (of string)

Represents the normal network phasing condition. If the attribute is missing, three phases (ABC) shall be assumed, except for terminals of grounding classes (specializations of EarthFaultCompensator, GroundDisconnector, and Ground) which will be assumed to be N. Therefore, phase code ABCN is explicitly declared when needed, e.g. for star point grounding equipment.
The phase code on terminals connecting same ConnectivityNode or same TopologicalNode as well as for equipment between two terminals shall be consistent.

Must be one of:

  • "ABCN"
  • "ABC"
  • "ABN"
  • "ACN"
  • "BCN"
  • "AB"
  • "AC"
  • "BC"
  • "AN"
  • "BN"
  • "CN"
  • "A"
  • "B"
  • "C"
  • "N"
  • "s1N"
  • "s2N"
  • "s12N"
  • "s1"
  • "s2"
  • "s12"
  • "none"
  • "X"
  • "XY"
  • "XN"
  • "XYN"

Type: integer

The orientation of the terminal connections for a multiple terminal conducting equipment. The sequence numbering starts with 1 and additional terminals should follow in increasing order. The first terminal is the "starting point" for a two terminal branch.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: array

State variable for status.

No Additional Items

Each item of this array must be:

Type: object

State variable for status.

Type: boolean

The in service status as a result of topology processing. It indicates if the equipment is considered as energized by the power flow. It reflects if the equipment is connected within a solvable island. It does not necessarily reflect whether or not the island was solved by the power flow.

Type: enum (of string)

The individual phase status. If the attribute is unspecified, then three phase model is assumed.

Must be one of:

  • "A"
  • "B"
  • "C"
  • "N"
  • "s1"
  • "s2"

Type: enum (of string)

SVC control mode.

Must be one of:

  • "reactivePower"
  • "voltage"

Type: object or number

The reactive power output of the SVC is proportional to the difference between the voltage at the regulated bus and the voltage setpoint. When the regulated bus voltage is equal to the voltage setpoint, the reactive power output is zero.

Type: enum (of string) Default: "none"

nan

Must be one of:

  • "p"
  • "n"
  • "micro"
  • "m"
  • "c"
  • "d"
  • "k"
  • "M"
  • "G"
  • "T"
  • "none"
  • "y"
  • "z"
  • "a"
  • "f"
  • "da"
  • "h"
  • "P"
  • "E"
  • "Z"
  • "Y"

Type: enum (of string) Default: "V"

nan

Must be one of:

  • "none"
  • "m"
  • "kg"
  • "s"
  • "A"
  • "K"
  • "mol"
  • "cd"
  • "deg"
  • "rad"
  • "sr"
  • "Gy"
  • "Bq"
  • "degC"
  • "Sv"
  • "F"
  • "C"
  • "S"
  • "H"
  • "V"
  • "ohm"
  • "J"
  • "N"
  • "Hz"
  • "lx"
  • "lm"
  • "Wb"
  • "T"
  • "W"
  • "Pa"
  • "m2"
  • "m3"
  • "mPers"
  • "mPers2"
  • "m3Pers"
  • "mPerm3"
  • "kgm"
  • "kgPerm3"
  • "WPermK"
  • "JPerK"
  • "ppm"
  • "rotPers"
  • "radPers"
  • "VA"
  • "VAr"
  • "cosPhi"
  • "Vs"
  • "V2"
  • "As"
  • "A2"
  • "A2s"
  • "VAh"
  • "Wh"
  • "VArh"
  • "VPerHz"
  • "HzPers"
  • "character"
  • "charPers"
  • "kgm2"
  • "dB"
  • "WPers"
  • "lPers"
  • "dBm"
  • "h"
  • "min"
  • "Q"
  • "Qh"
  • "ohmm"
  • "APerm"
  • "V2h"
  • "A2h"
  • "Ah"
  • "count"
  • "ft3"
  • "m3Perh"
  • "gal"
  • "Btu"
  • "l"
  • "lPerh"
  • "lPerl"
  • "gPerg"
  • "molPerm3"
  • "molPermol"
  • "molPerkg"
  • "sPers"
  • "HzPerHz"
  • "VPerV"
  • "APerA"
  • "VPerVA"
  • "rev"
  • "kat"
  • "JPerkg"
  • "m3Uncompensated"
  • "m3Compensated"
  • "WPerW"
  • "therm"
  • "onePerm"
  • "m3Perkg"
  • "Pas"
  • "Nm"
  • "NPerm"
  • "radPers2"
  • "WPerm2"
  • "JPerkgK"
  • "JPerm3"
  • "VPerm"
  • "CPerm3"
  • "CPerm2"
  • "FPerm"
  • "HPerm"
  • "JPermol"
  • "JPermolK"
  • "CPerkg"
  • "GyPers"
  • "WPersr"
  • "WPerm2sr"
  • "katPerm3"
  • "d"
  • "anglemin"
  • "anglesec"
  • "ha"
  • "tonne"
  • "bar"
  • "mmHg"
  • "M"
  • "kn"
  • "Vh"
  • "Mx"
  • "G"
  • "Oe"
  • "WPerA"
  • "SPerm"
  • "onePerHz"
  • "VPerVAr"
  • "ohmPerm"
  • "kgPerJ"
  • "JPers"
  • "m2Pers"
  • "JPerm2"
  • "KPers"
  • "PaPers"

Type: number Default: null

nan

Type: boolean

The aggregate flag provides an alternative way of representing an aggregated (equivalent) element. It is applicable in cases when the dedicated classes for equivalent equipment do not have all of the attributes necessary to represent the required level of detail. In case the flag is set to “true” the single instance of equipment represents multiple pieces of equipment that have been modelled together as an aggregate equivalent obtained by a network reduction procedure. Examples would be power transformers or synchronous machines operating in parallel modelled as a single aggregate power transformer or aggregate synchronous machine.
The attribute is not used for EquivalentBranch, EquivalentShunt and EquivalentInjection.

Type: boolean

The equipment is enabled to participate in network analysis. If unspecified, the value is assumed to be true.

Type: boolean

Specifies the regulation status of the equipment. True is regulating, false is not regulating.

Type: object or number

Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node.
Starting value for a steady state solution.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "VAr"

nan

Same definition as unit

Type: number Default: null

nan

Type: boolean

Specifies the availability of the equipment under normal operating conditions. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: string

The aliasName is free text human readable name of the object alternative to IdentifiedObject.name. It may be non unique and may not correlate to a naming hierarchy.
The attribute aliasName is retained because of backwards compatibility between CIM relases. It is however recommended to replace aliasName with the Name class as aliasName is planned for retirement at a future time.

Type: string

Master resource identifier issued by a model authority. The mRID is unique within an exchange context. Global uniqueness is easily achieved by using a UUID, as specified in RFC 4122, for the mRID. The use of UUID is strongly recommended.
For CIMXML data files in RDF syntax conforming to IEC 61970-552, the mRID is mapped to rdf:ID or rdf:about attributes that identify CIM object elements.

Type: string

The name is any free human readable and possibly non unique text naming the object.

Type: boolean

Specifies the availability of the equipment. True means the equipment is available for topology processing, which determines if the equipment is energized or not. False means that the equipment is treated by network applications as if it is not in the model.

Type: string

The description is a free human readable text describing or naming the object. It may be non unique and may not correlate to a naming hierarchy.

Type: object or number

Capacitive reactance at maximum capacitive reactive power. Shall always be positive.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "ohm"

nan

Same definition as unit

Type: number Default: null

nan

Type: object or number

Inductive reactance at maximum inductive reactive power. Shall always be negative.

Same definition as StaticVarCompensator.capacitiveRating

Type: object or number

The characteristics slope of an SVC defines how the reactive power output changes in proportion to the difference between the regulated bus voltage and the voltage setpoint.
The attribute shall be a positive value or zero.

Type: enum (of string) Default: "none"

nan

Same definition as multiplier

Type: enum (of string) Default: "VPerVAr"

nan

Same definition as unit

Type: number Default: null

nan